Page 10
Title
Low Profile Split Ducted Air Conditioner
4. Indoor Unit Installation
Low Profile Split Ducted Air Conditioner
1. Install a filter according to return air inlet size.
2. Return air inlet and supply air outlet duct should be
apart far enough to avoid air passage short-circuit.
3. Please refer to the following static pressure to install.
Change the fan motor static pressure corresponding
to external duct static pressure.
Change the fan motor static pressure corresponding to
external duct static pressure.
Model
Static Pressure (Pa)
LRE-071AS
0~135
LRE-100AS
0~155
LRE-130AS
0~195
LRE-170AS
0~200
Duct Installation
Adjust The Air Inlet Direction
Table 4.2
Table 4.3
External Static Pressure Settings
SP No.
External Static Pressure Parameters
LRE-071AS LRE-100AS LRE-130AS LRE-170AS
SP0
not used
SP 1
0 - 40 pa
0 - 40 pa
0 - 50 pa
0 - 60 pa
SP 2
40 - 70 pa
40 - 80 pa
50 - 90 pa
60 - 120 pa
SP 3
70 - 100 pa
80 - 120 pa
90 - 140 pa
120 - 140 pa
SP 4
100 - 135 pa
120 - 155 pa
140 - 195 pa
140 - 200 pa
Set External Static Pressure
Settings for external static pressure can be achieved by
using the wired controller supplied with the unit.
When the air conditioning unit is off, perform the next
steps:
- Press and hold “
COPY
” button for 3 seconds
- Press the button “
+
” or “
-
” to select the
SP
- Press the button “
CONFIRM
”
- Press the button “
+
” or “
-
” to select SP settings
The External Static Pressure setting is now complete.
1. Take off ventilation panel and flange.
2. Change the mounting positions of ventilation panel and
air return flange .
Fig.4.10
Fig.4.11
NOTE
All the figures in this manual are for explanation
purpose only. They may be slightly different from the air
conditioner you purchased.
When required the return air inlet direction can be adjusted
from rear-side to under-side using the following steps:
Return Air Inlet Flange
Return Air Inlet Flange
Ventilation panel
Ventilation panel
Note:
Not applicable to LRE-170AS.