Installation and Commissioning Guide
Wall Hung Split System
Installation and Commissioning Guide - Wall Hung Split System
Doc. No.9590-5007
Ver. 2 210416
27
10. Refrigeration Piping Connection
Outdoor Model
Indoor Model
WRC-026CS
WRE-026CS
WRC-035CS
WRE-035CS
WRC-050CS
WRE-050CS
WRC-072CS
WRE-072CS
WRC-085CS
WRE-085CS
Minimum Field Pipe Length - (m)
3
3
3
3
3
Maximum Field Pipe Length - (m)
25
25
30
50
50
Maximum Vertical
10
10
20
25
25
Field Pipe Size
Liquid Pipe -
mm (inch)
6.35 (1/4)
6.35 (1/4)
6.35 (1/4)
9.52 (3/8)
9.52 (3/8)
Gas Pipe - mm
(inch)
9.52 (3/8)
9.52 (3/8)
12.7 (1/2)
15.9 (5/8)
15.9 (5/8)
Outdoor Unit
Liquid Pipe -
mm (inch)
6.35 (1/4)
6.35 (1/4)
6.35 (1/4)
9.52 (3/8)
9.52 (3/8)
Gas Pipe - mm
(inch)
9.52 (3/8)
9.52 (3/8)
12.7 (1/2)
15.9 (5/8)
15.9 (5/8)
Indoor Unit
Liquid Pipe -
mm (inch)
6.35 (1/4)
6.35 (1/4)
6.35 (1/4)
9.52 (3/8)
9.52 (3/8)
Gas Pipe - mm
(inch)
9.52 (3/8)
9.52 (3/8)
12.7 (1/2)
15.9 (5/8)
15.9 (5/8)
NOTE
Ensure that the length of the refrigerant pipe, the number of bends, and the drop height between the indoor and outdoor
units meets the requirements shown in above table.
Refrigerant Piping Connection Instructions:
1. Cut the connecting pipes according to required length.
2. Remove burrs in the pipe. Burrs can affect the air-tight seal of refrigerant piping connections.
3. Place flare nuts on both ends of pipe. Flare each end of connecting pipes.
Flare nut
Copper
pipe
4. Connect the pipe to indoor and outdoor unit. Apply a thin coat of refrigeration oil to the flared end of the
pipe. Tighten the flare nuts using a spanner and torque wrench.
Unit tubing
Flare nut
Pipe