Installation and Commissioning Guide - Wall Hung Split System
Doc. No.9590-5007
Ver. 2 210416
Installation and Commissioning Guide
Wall Hung Split System
28
Pipe Flare Dimension and Tightening Torque Guide
Pipe
Size
Tightening
Torque
Flare Dimension
(A)
Flare Shape
Min
(mm)
Max
(mm)
0 6.35
18 - 20 Nm
8.3
8.7
0 9.52
32 - 39 Nm
13.2
13.5
0 12.7
49 - 59 Nm
16.2
16.5
0 16
57 - 71 Nm
19.2
19.7
CAUTION
• Ensure to wrap insulation around the piping. Direct contact with the bare piping may result in burns or frostbite.
• Make sure the pipe is properly connected. Over tightening may damage the bell mouth and under tightening may lead
to leakage.
Instructions for Connecting Piping to Outdoor Unit
1. Unscrew the valve cover on the side of the outdoor unit.
Valve Cover
Remove protective caps from ends of valves.
2. Align flared pipe end with each valve, and tighten the flare nut as tightly as possible by hand.
3. Using a spanner, grip the body of the valve. Do not grip the nut that seals the service valve.
NOTE
USE SPANNER TO GRIP MAIN BODY OF VALVE. Torque from tightening the flare nut can snap off other parts of valve
.