Installation and Commissioning Guide
Wall Hung Split System
Installation and Commissioning Guide - Wall Hung Split System
Doc. No.9590-5007
Ver. 2 210416
29
4. While firmly gripping the body of the valve, use a torque wrench to tighten the flare nut according to
the correct torque values.
5. Loosen the flaring nut slightly, then tighten again.
6. Repeat Steps 3 to 6 for the remaining pipe.
CAUTION
If the indoor unit is installed at a higher position than the outdoor unit , there is chance that oil may flow into the
compressor. This may cause liquid compression or deterioration of oil return. Use oil traps in the gas piping to prevent this.
An oil trap should be installed every 10m in the vertical suction line riser.
Oil Trap
Gas Piping
Indoor Unit
Liquid
Piping
Outdoor Unit
10m
10m