TECHNICAL SPECIFICATION
Description
These atmospheric burners are fitted with a SIT gas valve and an
electrically operated relay. This gas valve has been specially developed
for atmospheric burners with automatic ignition and ionisation flame
detection.
Advantage
•
No pilot flame, therefore no gas consumption when when the
boiler is off.
•
The burner only operates when there is a demand for hot water.
•
The electric ignition requires no action.
Starting
•
Flush the gas pipe thoroughly, turn on the room thermostat and
switch the control thermostat to heat demand.
•
Open the gas tap.
•
Turn on the main switch on the control panel.
The burner is preset at the factory.
Check the supply pressure and the pressure in the
burner when starting the boiler.
11
Fig. 17: Burner gas valve
Propane gas atmospheric burner
(fig.19)
1.
Burner plug connector
2.
Pot type flame holder
3.
Ignition and ionisation electrode
4.
Observation window
5.
Injector
6.
Relay
7.
Reset button
8.
Burner chamber plate
1. Ignition and ionisation electrode
2. Flame holder
3. Burner chamber plate
4.
Injectors
5. Reset button
6. Gas valve
7. Relay
8. Observation window
Natural gas atmospheric burner
(fig.18)
1
2
3
4
1
8
2
4
5
7
6
3
3
2
7
1
4
5
6
8
1. Electrically operated gas valves.
2. Upstream gas pressure test point.
3. Pressure regulator
4. Gas burner pressure test point.