background image

EN • 3

WHO SHOULD READ THESE INSTRUCTIONS

These instructions should be read by:
- the specifying engineer
- the installer
- the user
- the service engineer

SYMBOLS

RECOMMENDATIONS

 

•  These  instructions  are  an  integral  part  of  the  equipment  to 

which they refer and the user must be provided with a copy.

•  The  product  must  be  installed  and  serviced  by  qualified 

engineers, in compliance with current standards.

•  The  manufacturer  cannot  accept  liability  for  any  damage 

resulting  from  incorrect  installation  or  from  the  use  of 
components or fittings not specified by the manufacturer.

•  Any  failure  to  follow  instructions  relating  to  tests  and  test 

procedures may result in personal injury or risks of pollution.

 

• It is important to switch the boiler off before carrying out any 

work.

• There are no user parts inside the control panel.

APPLICABLE STANDARDS

The  products  described  in  this  document  have  been  certified  at 

European level “

CE

” (European Directives  

92/42/EEC

 “Efficiency”, 

90/396/EEC

  “Gas  devices”).  They  have  be  awarded  the  Belgian 

label 

“HR+”

 (gas boilers) and “

OPTIMAZ

” (oil boilers).

IMPORTANTS NOTES

These instructions are an integral part of the equipment to which 

they relate and must be handed to the user.

The product must be installed and serviced by qualified engineers 

in accordance with the regulations in force.

The manufacturer declines all liability for any damage caused as a 

result of incorrect installation or in the event of the use of appliances 

or accessories that are not specified by the manufacturer.

  The  manufacturer  reserves  the  right  to  change  the 

technical characteristics and specification of its products 

without notice.

WARNINGS

Danger of burns

Essential instruction for

the safety of persons

and the environment.

Danger of electrocution.

Essential instruction for

the correct operation

of the installation.

Summary of Contents for Delta F25

Page 1: ...excellence in hot water delta performance performance 25 35 45 55 F25 F35 F45 F55 G25 G35 G45 G55 16 12 2004 664Y0001 EN INSTALLATION OPERATING AND SERVICING INSTRUCTIONS ...

Page 2: ...m 9 Chimney connection 9 Heating system connection 10 Domestic hot water connection 10 Controller kits 11 Oil supply 11 ELECTRICAL CONNECTIONS 12 Electrical boiler connection 12 Electrical burners connection 12 OIL BURNER CHARACTERISTICS 13 Description 13 Setting oil burner parametres 13 GAS BURNER CHARACTERISTICS 14 ACV BG 2000 S Air Gas premix gas burner 14 Setting gas burner parametres 14 Gas c...

Page 3: ...ol panel APPLICABLE STANDARDS The products described in this document have been certified at European level CE European Directives 92 42 EEC Efficiency 90 396 EEC Gas devices They have be awarded the Belgian label HR gas boilers and OPTIMAZ oil boilers IMPORTANTS NOTES These instructions are an integral part of the equipment to which they relate and must be handed to the user The product must be i...

Page 4: ...le command the water temperature of both the primary circuit and the domestic hot water circuit can be set by the adjustable thermostat situated underneath the tank in the primary circuit A cut off thermostat placed on the top of the boiler automatically switches off the burner when the temperature of the water in the primary circuit reaches 95 C A manually resetable safety thermostat switches off...

Page 5: ...stion chamber Boiler drain cock Inner annular tank containing a domestic hot water Polyurethane foam insulation Outer body containing the primary water Base Detachable front panel Burner cover Manual reset high limit thermostat 103 C Control panel Side casing Burner chamber plate Control thermostat bulb Bulb of the thermal reset high limit thermostat 95 C Chimney reducing pipe ...

Page 6: ... Summer Winter switch Switches ON and OFF the heating pump 4 Thermometer The thermometer shows the boiler temperature in the heating circuit This temperature should not exceed 90 C If it does stop the boiler and check the settings on the thermostat If the problem persists contact your installer for advice 5 ACV climatic controller optional Refer to the instructions supplied with the controller if ...

Page 7: ...ate the boiler s electrical supply at the switch on the external control box before removing the front panel of the casing for press the manual reset high limit thermostat on the top of the boiler Manual reset high limit thermostat Wait until the boiler temperature drops to below 60 C then refit the front panel of the casing If the problem persists please contact your installer for advice Starting...

Page 8: ...25 35 45 55 F25 F35 F45 F55 G25 G35 G45 G55 A mm 1497 1697 1497 1697 1497 1697 1497 1697 1497 1697 1497 1697 B mm 130 130 150 150 130 130 150 150 130 130 150 150 C mm 360 360 390 390 360 360 390 390 360 360 390 390 D mm 565 565 565 565 818 818 818 848 755 755 755 755 Weight when empty kg 145 156 168 200 157 168 180 212 159 170 182 214 GENERAL The appliances are supplied fully assembled tested and ...

Page 9: ...0 mm To the rear 150 mm To the sides 100 mm Above 700 mm Base The base on which the boiler will be mounted must be made from non combustible materials Ventilation The boiler room must have both low and high level ventilation By way of information the table below gives the minimum ventilation requirements according to Belgian regulations The user must ensure that his boiler room ventilation complie...

Page 10: ...and calibrated to 7 bar the group s valve discharge must be connected to the sewer HOT WATER EXPANSION VESSEL Installing a hot water expansion vessel will prevent any risk of excess pressure due to water hammer or pressure fluctuations HOT WATER CIRCULATION If the water tank is a long way from the point of use installing a closed recirculation circuit can ensure a faster hot water drawoff at any t...

Page 11: ...door sensor 30 50 C a servomotor SQY 349 230 V 3 pin and an intermediate socket CIRCUIT DIAGRAM OF ACV CONTROL KITS B2 Temperature sensor B9 Outdoor sensor B5 Analog digital room sensor P1 Pump Y1 Y2 N Servomotor SSY 319 or SQK 349 bl Blue N n z Black Y2 br Brown Y1 Please contact your installer for further details about this 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 20 19 18 17 16 15 14 ...

Page 12: ...9 Thermal reset high limit thermostat 95 C B Blue Br Brown Bk Black Or Orange Y Gr Yellow Green The boiler must be isolated from the electrical supply before any work is carried out on it 1 2 C L1 L1 N T1 T2 N T1 T2 S3 S3 S3 B4 N T1 T2 L1 1 4 9 2 3 7 5 8 6 230V 50 Hz 6A Br Bk Bk Br Or Y Gr B Br B Or B Y Gr B Br B Y Gr Br Or Or B Or ELECTRICAL BURNERS CONNECTION PH Phase N Neutral M Motor VM1 Magne...

Page 13: ...lame by an insulation blanket SETTING OIL BURNER PARAMETERS F25 F35 F45 F55 Burner BM R 31 BM R 31 BM R 51 BM 101 Output kW 12 48 12 48 42 60 55 130 Electrical power W 150 150 150 185 Nozzle gal h 0 6 0 75 0 85 1 50 Nozzle angle 60 60 60 B 60 B Oil flow rate kg h 2 18 2 84 3 60 5 76 Pump pressure bar 11 2 12 0 15 0 10 0 Flue gas index 0 6 0 3 0 4 0 5 Air flap setting 4 5 4 8 4 5 5 0 Combustion head ...

Page 14: ...charging of the burnt gases the air flow drops and this leads to the same reactions as those described above leading to the burner being shut down locked out SETTING OIL BURNER PARAMETERS G25 G35 G45 G55 Burner BG 2000 S 25 BG 2000 S 35 BG 2000 S 45 BG 2000 S 55 Input kW 25 34 9 45 55 Output kW 22 45 31 35 40 5 49 Combustion efficiency natural gas 91 7 91 5 92 4 92 CO2 natural gas 9 1 9 0 8 9 9 0 C...

Page 15: ...ctor Ø 3 4 Ionisation electrode Venturi Fan Burner chamber plate insulation Burner chamber plate sealing cord Gas valve Burner chamber plate Flame inspection window Burner tube Potentiometer setting Electrical burner connector Ignition cable Ionisation cable Control monitoring relay ...

Page 16: ...clean them Replace these items if worn 6 Remove the burner cover and burner E 7 Brush the flue ways D 8 Clean the combustion chamber F and the burner 9 Check the condition of the seal on the burner chamber plate H MAINTENANCE OF BURNER See the technical and maintenance manual of the burner MAINTENANCE OF SAFETY EQUIPMENT Check that all thermostats and safety devices operate correctly boiler thermo...

Page 17: ...EN 17 COMMISSIONING AND MAINTENANCE 8 8 4 3 1 2 5 6 9 7 4 5 3 11 8 10 6 9 7 5 2 1 F D C E A B G H ...

Page 18: ...EN 18 ...

Page 19: ...39 21471339 21471338 21471338 21471339 21471339 A05 21474338 21474338 21474339 21474339 21474338 21474338 21474339 21474339 A06 21475338 21475338 21475338 21475338 21475338 21475338 21475338 21475338 A07 21478338 21478338 21478338 21478338 21478338 21478338 21478338 21478338 A08 21476339 21476338 21476339 21476338 21476339 21476338 21476339 21476338 A09 21477338 21477338 21477338 21477338 21477338...

Page 20: ...66016 54766016 54766017 54766017 54766017 54766017 54442045 54442045 54442045 54442045 54764021 54764021 54764021 54764021 54763007 54763007 54763007 54763007 54322000 54322000 54322000 54322000 54764010 54764010 54764010 54764010 54428129 54428129 54428129 54428129 49410045 49410045 49410045 49410039 ...

Page 21: ...F3033 557A0016 557A0016 507F2005 507F2005 507F2005 507F2005 51305000 51305000 51305000 51305000 55426001 55426001 55426001 55426001 63438001 63438001 63438001 63438001 47438008 47438008 47438008 47438008 47405004 47405004 47405004 47405004 47405005 47405005 47405005 47405005 ...

Page 22: ...F25 F35 F45 F55 BM R 31 237E0009 237E0009 BM R 51 23860600 BM 101 23860200 G25 G35 G45 G55 BG 2000 S 25 237D0063 BG 2000 S 35 237D0066 BG 2000 S 45 237G0065 BG 2000 S 55 237D0013 ...

Page 23: ...SA TEL 1 856 228 8881 FAX 1 856 228 3584 E MAIL sales triangletube com excellence in hot water www acv world com ARGENTINA TECNOPRACTICA ALFEREZ BOUCHARD 4857 1605 CARAPACHAY BUENOS AIRES TEL 54 11 47 65 33 35 FAX 54 11 47 65 43 07 E MAIL jchas tecnopractica com AUSTRALIA HUNT HEATING PTY LTD 10 GARDEN BOULEVARD 3172 VICTORIA AUSTRALIA TEL 61 3 9558 7077 FAX 61 3 9558 7027 E MAIL enquiries hunthea...

Reviews: