1
1
2
3
2
3
WaterMaster® 25 (X) - 35 - 45 (X) Evo
WaterMaster® 70 (X) - 85 Evo
Min. 3 mm
Max. 4 mm
Min. 3 mm
Max. 4 mm
1
2
3
WaterMaster® 120 Evo
40
A1009341-664Y8300 • B
REMOVAL, CHECK AND INSTALLATION
OF THE BURNER ELECTRODE
Remove the electrode to control it in case of
ignition problems.
Set-up conditions
•
Appliance shut down
•
External power supply isolated
•
Gas supply closed
•
Top panel open, refer to ML booklet.
Removal procedure
1. Disconnect the electrode grounding cable from
the electrode.
2. Disconnect the electrode ignition cable from the
electrical box.
3. Remove two mounting screws (
1
) and retain them
for reinstallation.
4. Remove the electrode (
2
) and the gasket (
3
).
5. Check the correct alignment of the electrode
ends and that the gap corresponds to the values
indicated on the figure below.
6. If the electrode is in bad condition, replace it.
Installation procedure
1. Install a new gasket (
3
).
2. Install the electrode (
2
) using the two screws (
1
),
torque i.a.w.
.
Follow-on tasks
1. Reconnect the grounding cable to the electrode.
2. Reconnect the ignition cable to the electrical
box.
EN
Maintenance
Summary of Contents for WaterMaster 120 Evo
Page 48: ...ACV International Oude Vijverweg 6 B 1653 Dworp Belgium belgium service acv com www acv com...
Page 49: ...A1009341_664Y8300 B WaterMaster 25 35 45 70 85 120 Evo 25 45 70 X Evo ML...
Page 57: ...9 x4 x4 x4 1 2 x2 ML...
Page 59: ...11 x7 WM 25 35 45 Evo x9 WM25X 45X 70 85 120Evo x11 WM 70 X Evo x3 x2 ML...
Page 60: ...12 WaterMaster 70 X Evo x4 ML...
Page 61: ...13 6 3 2 1 x4 x4 WaterMaster 25 X 35 45 X 70 85 120 Evo ML...
Page 75: ...31 ML...
Page 76: ...ACV International Oude Vijverweg 6 B 1653 Dworp Belgium belgium service acv com www acv com...