Chapter 1 Principles
CPU ADAM 821x
1-8
ADAM 8000 Manual CPU 821x – Rev 1.1
Hints for project engineering
For the project engineering of the CPU 821x and the other System 82xx
modules connected to the same bus, you use the hardware configurator
from Siemens.
To address the directly plugged peripheral modules, you have to assign a
special address in the CPU to every one.
The address allocation and the parameterization of the modules takes
place in the STEP
7 manager from Siemens in form of a virtual Profibus
system. For the Profibus interface is standardized software sided, the
functionality is guaranteed by including a GSD-file into the STEP
7
manager from Siemens.
Transfer your project into the CPU via the MPI interface.
For the project engineering of your CPU 821x the following requirements
have to be fulfilled:
•
STEP
7 manager from Siemens is installed at your PC resp. PU.
•
The GSD-file for the System 82xx is included to the hardware
configurator
•
serial connection to the CPU (e.g. via "Green Cable")
Note!
The configuration of the CPU requires a thorough knowledge of the
Siemens STEP
7 manager and the hardware configurator!
The CPU 821x is configurable via the STEP7
®
manager from Siemens.
This means the programming and parameterization of a System ADAM
82xx and the parameterization and project engineering under Profibus-DP.
The project engineering of a CPU 821x takes place via the STEP
®
7 mana-
ger from Siemens in form of a virtual Profibus system with the CPU 315-
2DP as basic.
Due to the standardized Profibus interface ADAM is able to support the
complete functionality of the System 82xx family in the STEP
®
7 manager
from Siemens by including a GSD-file.
To be compatible with the STEP
7 configuration tool from
Siemens, the following steps have to take place:
•
Project the Profibus-DP master system with CPU 315-2DP
(6ES7 315-2AF01).
•
Add Profibus slave with address 1.
•
Include the CPU 821x at slot 0 of the slave system.
Outline
Preconditions
Compatibility to
STEP
7 manager
from Siemens via
GSD-file