Manual AD-MM 500 FE
Parametername
Default value
Range
Unit
Log mode
Continuous
Continuous,
Hysteresis,
Window,
Trend Rising,
Trend falling,
Trend equal,
Interval once,
Interval daily,
Start time continuous
Trigger channel
1
1 ... 32
Limits
0.0...1.0
float range
trigger
chan-
nel
Trend delta
1,0
1E-6...1E6
trigger
chan-
nel
Trend time
10
1...3600
s
Start time one-time
11.11.2018 11:11:11
End time once
11.11.2018 11:11:12
Start time daily
11.11.2018 11:11:11
End time daily
11.11.2018 11:11:12
Start time continuous
11.11.2018 11:11:12
To start and stop the logging process quickly, use the parameter
Log
Release
.
Continuous logging
If logging is to be continuous and without condition, the following parameters must be set.
1.
Log mode
= ’
Continuous
’
2.
Log enable
= ’
Yes
’
The trigger conditions for limit, trend and time are not considered. The log operation starts
immediately and does not end until
Log enable
= ’
No
’ is set or another log mode is selected.
Hysteresis-triggered logging
If the trigger condition is to be done by a hysteresis function, the following parameters must be
set.
1.
Log mode
= ’
Hysteresis
’
2.
Trigger channel
= ’
1...32
’. Channel number for determining the value
3.
Limits
= ’
Your values for lower and upper limit
’
4.
Log enable
= ’
Yes
’
19 / 36
1.0 2021-05-19