In the case of the drag pointer display, the min and max values since the last time the drag pointer
was reset or the restart of the AD-MM 500 FE are displayed. The drag pointer can be reset via
the main menu of the AD-MM 500 FE . The values for determining the minimum and maximum
values are always determined automatically from all channels that are queried.
7.4 Channels
There are 32 channels that can be freely configured. The channels save all parameters that
the AD-MM 500 FE needs to acquire a value via Modbus. The following parameters can be
configured for each channel.
Parametername
Default value
Range
Unit
Slave address[N]
1
1 ... 247
Holdingregister[N]
0 ... 65535
Data type [N]
Single
U08, S08, U16, S16,
U32, S32, Single
Log interval[N]
5
1 ... 65535
s
Log enable[N]
No
No, Yes
Label[N]
’Channel N’
0 ... 20
characters
Unit[N]
’?’
0 ... 10
characters
[N] is the 1-based index of the channel [1..32].
Example settings: Slave address=2, Holdingregister=41120, Data type=single, Log interval=10.