7 Configuration
The information in this chapter refers to the configuration of the AD-MM 500 FE with the Config-
uration program AD-Studio . All the designations used can be found there. The configuration of
the parameters via the menu of the AD-MM 500 FE is not possible due to the large number of
parameters.
7.1 Logging
Whether to log is determined once per second, see picture 7.1. Logging can be done permanently
without a condition or conditionally. Conditional logging can be controlled by a limit value, a trend
or by a time condition. It also checks the availability of the hardware.
Grenzwert-Trigger,
Trend-Trigger
Zeit-Trigger
Hardwarestatus
RTC
EEPROM
SD-Karte
Hysterese
Fenster
Trend steigend
Trend fallend
Trend gleich
Intervall einmalig
Intervall täglich
Startzeit dauernd
Zeitstempel
Log-Modus
Triggerkanal
Kanal[1]
Kanal[32]
&
Log-Freigabe
Triggerung
Hardware OK
Loggen
1/s
Dauernd
Figure 7.1:
Determining the log enabling of the AD-MM 500 FE
The following parameters are provided to control logging:
Parametername
Default value
Range
Unit
Log enable
No
No,
Yes