USER’S MANUAL V-line 899x.xxx/LPG
21
15.
PUTTING OF THE DISPENSER INTO OPERATION
Entire hydraulic system of the LPG module has to be subjected to the pressure test by nitrogen of 2,5 MPa
pressure. Being the test pressure attained, check all joints of the hydraulic system by a foaming agent.
Wiring inspection of the dispenser unit has to be carried out.
All functional tests and inspections are carried out under the supervision of a Technical Inspection
Institute inspector who will issue a test certificate about tests and inspections.
Being the pressure test and inspection finished and positive results obtained, the hydraulic circuit of the
LPG module can be filled with liquid gas.
The inspection of wiring and the pressure test of the LPG module can only be performed by a person
provided with a certificate for this activity issued by the state inspection agency.
15.1.
Putting of the dispenser and electronic counter into operation
Switch on the feeding of the dispenser in the switchboard of the filling station (feeding of the
electronics and el. motor of the LPG pump).
The octal test of the counter will be performed after depressing or switching over the LPG
switch and if the LPG dispensing nozzle is connected to the vehicle tank, it is possible to
perform filling.
Switch off the LPG switch.
In case the dispenser is switched with the LPG switch on, it is necessary to switch off an on
this switch and again to activate the dispenser (counter resetting).
Now it is possible to start fuel filling.
15.2.
Shutdown of the dispenser and electronic counter
Switch the feeding of the dispenser in the switchboard of the filling station off (feeding the
electronics and el. pump motor).
15.3.
Restart of the dispenser and electronic counter after power failure and
voltage drop
In case of power failure or voltage alteration beyond acceptable limits the information about
the volume and price of the fuel dispensed within the interval from the last button pressing
or switch–over of switch into the ON position is preserved on the counter display.
In case power failure has occurred in the very time of fuel filling, it is necessary to button
release or switch off the LPG switch and cash in the sum, which is preserved on the display.
After el. power supply recovery the electronic counter is ready-to-start and fuel filling can
continue by button pressing or switching the LPG switch on.
16.
PACKING AND STORAGE
16.1.
Packing
The packing of dispensers differs in dependence on the point of destination. Dispensers for home market
are packed up in bubble wrap, while cardboard wrapping is mostly used for abroad. On preliminary
agreement of the customer the dispensers delivered abroad can be also packed up in bubble wrap or
other similar packing.
1.1.
Storage
Max. storage time under the shelter is 3 months and 1 month for outdoor storage with bubble wrapping.
Max. storage time under the shelter is 6 months with cardboard packing.
17.
GUARANTEE AND RECLAMATION
The dispenser reliable operation and service life depend on its proper servicing and maintenance.
This
is
why every individual who operates, checks or maintains the dispenser, should be acquainted with all
principles of correct operation, safety, revisions, and maintenance, and with relevant regulations on
handling liquefied gas. Particularly important it is necessary to keep the intervals of revisions and checks
defined by the plan of maintenance.