2.3 Installation
Installation is identical for all AGLAS Remote versions.
Figure 8:
Diagram of AGLAS installation in series circuit
2.3.1 Installation in a Transformer Pit
The orientation required for installation is indicated by the labeling on the nameplate.
This ensures optimum heat dissipation through the housing. If the device is installed by suspension, free air circulation must be
provided for the AGLAS Remote.
NOTE:
If several AGLAS Remotes are installed in a single pit, they should be spaced with a distance of at least 2-inch (50mm) from
each other and from the series transformers to have optimum communication signal separation. Because the communication
signal is coupled magnetically, the distance between the transformers should also not be less than 2-inch (50mm).
Minimum distance between remote cable feed-through and pit walls is 2-inch (50 mm).
Figure 9:
Remote max. bending radius
1. Light Fixture
5. Remote Input Plug (TRANSFORMER)
2. Light Fixture Plug
6. Transformer Secondary Receptacle
3. Remote Output Receptacle (LAMP)
7. Primary Series Circuit
4. Remote
8. L-830/L-831 Isolation Transformer
1
2
3
5
6
7
8
Earth
Ground
2-inch (50 mm)
radius