AGLAS-C Remote Control Device
Installation
© ADB SAFEGATE All Rights Reserved
14
96A0481 Rev. A
2.3.2 Connection to the Series Transformer and the Light Fitting(s)
The 2-pin plug on cable X1 is connected to the socket for the secondary circuit of the series transformer. The light(s) is/are
connected to the 2-pin socket(s) of the cable(s) X3 (and X4 for the dual AGLAS Remote).
All plug connections must be sealed with self-bonding insulation tape or using “heat shrink” sleeves.
To improve watertightness, an optional watertight heat shrink sleeve can be installed at the junction of the plug and receptacle:
(see Figure 10)
Figure 10:
Connection to series transformer and light fitting
Step 1:
Place the heat shrink sleeve over the light inset plug wire.
Step 2:
Connect the inset light plug to the Remote receptacle designated CHANNEL A (and CHANNEL B if used).
Step 3:
Pull the heat shrink sleeve over the plug-to-receptacle connection. Heats shrink the sleeve.
Repeat steps 1 through 3 for the Remote plug designated TRANSFORMER and the transformer secondary receptacle.
Watertight heat shrink sleeve
Plug and Receptacle
Step 3
Step 2
Step 1