Check at brightness steps 2 and 3
4. Repeat the procedure with the rotary switch of the LMC in positions 2 and 3.
7.7 Measure power draw
Measure power draw on power supply that feeds flashing system
1. Measure the current on all phases. Use a True RMS current clamp.
2. Check the current:
•
For an equal number of units distributed over the 3 phases, make sure the current is less than 1 A RMS;
•
If there is a loading difference between the phases, make sure that it is less than 2.5 A RMS.