2.0 Airfield Lighting Field Lightning Arrestor

Airfield Lighting Field Lightning Arrestor (FLA) is designed to help reduce the susceptibility of airfield series circuits to

lightning strikes or surges. The FLA is designed to be installed at 600m (2000 ft) intervals in the 5KV airfield primary series

circuit but can be installed at closer intervals as desired. Each FLA adds additional local protection against damage from

lightning strikes reducing the risk of widespread damage in the field and to equipment in the electrical vault.

2.1 Field Lightning Arrestor

Compliance with Standards

FAA:

Complies with AC 150/5345-10, Section 3.4.12 (Lightning/Surge Arrestors)

Overview

For use on airfield series circuits to further reduce the risk of lightning damage on the series circuit

Can be inserted at various points in the 5 kV airfield primary series circuit to provide additional lightning protection.

Can be used on any airfield circuit (6.6 A from 4 kW to 30 kW and 20 A from 15 kW to 70 kW)

Rated for 25,000 A peak (8/20 microsecond discharge)

Assembly rated NEMA 6P

Insulation resistance is 10 GΩ (minimum)

Includes a UL 467 rated ground lug, which accepts an AWG 4 to AWG 14 earth ground wire

Operating temperature: -55 °C to +55 °C (-67 °F to +131 °F)

Installation

It is recommended that the field lighting arrestor be installed a maximum of about every 2,000 feet around the series circuit,

starting at the first base can closest to the vault on each leg of the series circuit. Simply disconnect (unplug) the L-823

connectors at the designated point and plug in the field lighting arrestor. Connect a known good earth ground (25 Ω or less)

to the earth ground lug of the field lighting arrestor using at least an AWG 6 wire.
The field lightning arrestor can be installed in a base can (preferred) or direct earth buried. Heat shrink each L-823 connector

interface using an airport approved method. The field lighting arrestor body is waterproof (rated NEMA 6P) and is fully

resistant to deicing fluids.

Ordering Code 

 

44A6102

Maintenance

There are no internal repairable parts since the field lighting arrestor is completely sealed. If the field lighting arrestor fails,

replace it with a new one. Note that the heat sink on a field lighting arrestor is colored red in order to differentiate it from the

ADB Safegate BRITE Remote. An ADB Safegate BRITE Remote has a silver colored heat sink.

Troubleshooting

The field lighting arrestor contains Metal Oxide Varistor (MOV) components similar to the type used on the output of

Constant Current Regulators. A degraded or failed field lightning arrestor is typically evidenced by a rapid drop in the overall

series circuit insulation resistance. Troubleshoot using same techniques used to find failed isolation transformers.
One or more shorted field lighting arrestors may cause a section of lights to be dim or out. If it is suspected that the field

lighting arrestor has internally shorted, measure between the male L-823 and the arrestor earth ground lug using an

ohmmeter. The meter should read a very high resistance. A failed unit will read a very low resistance or zero ohms.

96A0489, Rev. B, 2018/03/06

5

Copyright 

©

 2017–2018 ADB Safegate, All Rights Reserved

Summary of Contents for FLA

Page 1: ...Airfield Lighting Field Lightning Arrestor User Manual 96A0489 Rev B 2018 03 06 ...

Page 2: ......

Page 3: ... guaranteed to be merchantable and fit for the ordinary purposes for which such products are made ADB SAFEGATE L858 Airfield Guidance Signs are warranted against mechanical and physical defects in design or manufacture for a period of 2 years from date of installation per FAA AC 150 5345 44 applicable edition Note See your sales order contract for a complete warranty description All Products Guara...

Page 4: ...eplacement parts or accessories Failing to make sure that auxiliary equipment complies with approval agency requirements local codes and all applicable safety standards if not in contradiction with the general rules Using materials or auxiliary equipment that are inappropriate or incompatible with your ADB SAFEGATE equipment Allowing unskilled personnel to perform any task on or with the equipment...

Page 5: ...tric Shock Hazard 3 2 0 Airfield Lighting Field Lightning Arrestor 5 2 1 Field Lightning Arrestor 5 2 2 Introduction 6 3 0 Installation 7 3 1 Introduction to Safety 7 3 2 Inspection on Arrival 7 3 3 Storage 8 3 4 Installation Procedures 8 3 5 Equipment Specification Data 9 4 0 Troubleshooting 11 96A0489 Rev B 2018 03 06 v Copyright 2017 2018 ADB Safegate All Rights Reserved ...

Page 6: ...Airfield Lighting Field Lightning Arrestor TABLE OF CONTENTS vi Copyright 2017 2018 ADB Safegate All Rights Reserved ...

Page 7: ...erve this warning may result in personal injury death or equipment damage ARC Flash may cause blindness severe burns or death WARNING Wear personal protective equipment Failure to observe may result in serious injury WARNING Do not touch Failure to observe this warning may result in personal injury death or equipment damage CAUTION Failure to observe a caution may result in equipment damage Qualif...

Page 8: ...ility and cover removal Protect equipment with safety devices as specified by applicable safety regulations If safety devices must be removed for installation install them immediately after the work is completed and check them for proper functioning prior to returning power to the circuit Failure to follow this instruction can result in serious injury or equipment damage Additional Reference Mater...

Page 9: ... is operating Arc flash may result Disconnect and lock out electrical power Always use safety devices when working on this equipment Follow the recommended maintenance procedures in the product manuals Do not service or adjust any equipment unless another person trained in first aid and CPR is present Connect all disconnected equipment ground cables and wires after servicing equipment Ground all c...

Page 10: ...Airfield Lighting Field Lightning Arrestor Safety 4 Copyright 2017 2018 ADB Safegate All Rights Reserved ...

Page 11: ...ug the L 823 connectors at the designated point and plug in the field lighting arrestor Connect a known good earth ground 25 Ω or less to the earth ground lug of the field lighting arrestor using at least an AWG 6 wire The field lightning arrestor can be installed in a base can preferred or direct earth buried Heat shrink each L 823 connector interface using an airport approved method The field li...

Page 12: ...th ground lug Meg the field lightning arrestor at 1000 VDC for one minute Replace the field lightning arrestor if resistance is less than 2 GΩ 2 2 Introduction The Field Lightning Arrestor incorporates distribution class Metal Oxide Varistors MOVs When a voltage transient occurs the impedance of the MOVs changes from a near open circuit to a highly conductive path to ground clamping the voltage to...

Page 13: ... must meet local codes Route electrical wiring along a protected path Make sure they will not be damaged by moving equipment Protect components from damage wear and harsh environment conditions Allow ample room for maintenance panel accessibility and cover removal Protect equipment with safety devices as specified by applicable safety regulations If safety devices must be removed for installation ...

Page 14: ...nection from the airfield series circuit This could be from the L 830 isolation transformer or a splice found in the light base 3 Plug in the lightning arrestor as shown in the wiring diagram See Figure 1 and hook up label on enclosure 4 After the connection has been made reinstall heat shrink in accordance with local heat shrinking practice 5 Check site plan drawings and specifications to verify ...

Page 15: ...rrestor part AD071P01 Customer Supplied Connection 6 AWG min Counterpoise or Copper clad Ground Rod L 830 Field Lightning Arrestor Rating 5KV 20 A Part AD071P01 3 5 Equipment Specification Data Table 1 Operating Specification Model FLA Nominal Voltage 6 KV Continuous Operation Voltage 5 1 KV Duty Cycle 10 kA crest 20 current surges 40 kA crest 2 current surges 8 20 µs waveshape High Current Discha...

Page 16: ...Airfield Lighting Field Lightning Arrestor Installation 10 Copyright 2017 2018 ADB Safegate All Rights Reserved ...

Page 17: ...ting series circuit wiring or isolation transformers See FAA Advisory Circular 150 5340 26 current edition for series circuit troubleshooting guidance Note Series circuit insulation resistance is normally tested using either 500Vdc or 1000Vdc The insulation resistance of series circuits with Field Lightning Arrestors can be tested with voltages up to 5000Vac or 7070Vdc The following physical evide...

Page 18: ...resistance should be greater than 2G ohms If the resistance is less than 2G ohms replace the FLA Figure 2 FLA Field Insulation Resistance Check Megger Jumper Airfield Lighting Field Lightning Arrestor Troubleshooting 12 Copyright 2017 2018 ADB Safegate All Rights Reserved ...

Page 19: ...230 USA Contact Tel 1 614 861 1304 Fax 1 614 864 2069 Email adb sales us adbsafegate com Internet www adbsafegate com ADB Safegate Airfield Technologies Ltd China ADB Safegate China Address Unit 603 D Block CAMIC International Convention Center No 3 Hua Jia Di East road ChaoYang district Beijing 100102 P R China Contact Tel 86 10 8476 0106 Fax 86 10 8476 0090 Email china safegate com Internet www ...

Page 20: ......

Reviews: