3.3 Storage

CAUTION

IMPROPER STORAGE

If equipment is to be stored prior to installation, it must be protected from direct sunlight.

Failure to follow this instruction can result in equipment damage

For proper storage, place the box of the product on a shelf or in a warehouse.

3.4 Installation Procedures

WARNING

• Protect from electrostatic discharge.
• The Field Lightning Arrestor assembly must be grounded to a low resistance earth ground.
• Failure to ground the FLA assembly will result in no added protection to the circuit.

Failure to follow this instruction can result in equipment damage

To install the Field Lightning Arrestor (FLA) into the series circuit, perform the following procedure:

1. Determine the specific location for the FLA to be installed in the circuit.

Note

It is recommended that the Field Lightning Arrestor assembly be installed approximately every 2000 feet around

the series circuit starting at the first useable L867/L868 light base can outside the vault on each side of the series

circuit. At the airport’s option, Field Lightning Arrestors may be installed more frequently if it is desired to further

reduce lightning risk.

2. Remove the light fixture from the L867/L868 light base can and disconnect one L-823 connection from the airfield series

circuit. This could be from the L-830 isolation transformer or a splice found in the light base.

3. Plug in the lightning arrestor as shown in the wiring diagram. See 

Figure 1

 and hook-up label on enclosure.

4. After the connection has been made, reinstall heat shrink (in accordance with local heat shrinking practice).
5. Check site plan drawings and specifications to verify the presence and location of the counterpoise lightning wire. Wiring

intended to be connected to a safety ground should not normally be attached to the FLA. See FAA AC 150/5340-30

(current edition) for further discussion about lightning and safety grounds on series circuits.

Note

IF COUNTERPOISE LIGHTNING WIRE IS PRESENT, connect a 4 AWG (minimum) copper grounding wire, to the

ground screw on end of the FLA enclosure and attach the other end of the ground wire to the counterpoise wire

using an appropriate attachment method.

Note

IF COUNTERPOISE LIGHTNING WIRE IS NOT PRESENT, an 8 ft. (min) long copper clad steel grounding rod may

have to be added in the vicinity of the FLA. It may be possible in some locations to add the ground rod through a

pre-existing hole in the bottom of the light base can. Connect ground wire between the grounding screw on the

enclosure using a UL 467 ground lug, or equivalent, and the grounding rod.

Airfield Lighting Field Lightning Arrestor
Installation

8
Copyright 

©

 2017–2018 ADB Safegate, All Rights Reserved

Summary of Contents for FLA

Page 1: ...Airfield Lighting Field Lightning Arrestor User Manual 96A0489 Rev B 2018 03 06 ...

Page 2: ......

Page 3: ... guaranteed to be merchantable and fit for the ordinary purposes for which such products are made ADB SAFEGATE L858 Airfield Guidance Signs are warranted against mechanical and physical defects in design or manufacture for a period of 2 years from date of installation per FAA AC 150 5345 44 applicable edition Note See your sales order contract for a complete warranty description All Products Guara...

Page 4: ...eplacement parts or accessories Failing to make sure that auxiliary equipment complies with approval agency requirements local codes and all applicable safety standards if not in contradiction with the general rules Using materials or auxiliary equipment that are inappropriate or incompatible with your ADB SAFEGATE equipment Allowing unskilled personnel to perform any task on or with the equipment...

Page 5: ...tric Shock Hazard 3 2 0 Airfield Lighting Field Lightning Arrestor 5 2 1 Field Lightning Arrestor 5 2 2 Introduction 6 3 0 Installation 7 3 1 Introduction to Safety 7 3 2 Inspection on Arrival 7 3 3 Storage 8 3 4 Installation Procedures 8 3 5 Equipment Specification Data 9 4 0 Troubleshooting 11 96A0489 Rev B 2018 03 06 v Copyright 2017 2018 ADB Safegate All Rights Reserved ...

Page 6: ...Airfield Lighting Field Lightning Arrestor TABLE OF CONTENTS vi Copyright 2017 2018 ADB Safegate All Rights Reserved ...

Page 7: ...erve this warning may result in personal injury death or equipment damage ARC Flash may cause blindness severe burns or death WARNING Wear personal protective equipment Failure to observe may result in serious injury WARNING Do not touch Failure to observe this warning may result in personal injury death or equipment damage CAUTION Failure to observe a caution may result in equipment damage Qualif...

Page 8: ...ility and cover removal Protect equipment with safety devices as specified by applicable safety regulations If safety devices must be removed for installation install them immediately after the work is completed and check them for proper functioning prior to returning power to the circuit Failure to follow this instruction can result in serious injury or equipment damage Additional Reference Mater...

Page 9: ... is operating Arc flash may result Disconnect and lock out electrical power Always use safety devices when working on this equipment Follow the recommended maintenance procedures in the product manuals Do not service or adjust any equipment unless another person trained in first aid and CPR is present Connect all disconnected equipment ground cables and wires after servicing equipment Ground all c...

Page 10: ...Airfield Lighting Field Lightning Arrestor Safety 4 Copyright 2017 2018 ADB Safegate All Rights Reserved ...

Page 11: ...ug the L 823 connectors at the designated point and plug in the field lighting arrestor Connect a known good earth ground 25 Ω or less to the earth ground lug of the field lighting arrestor using at least an AWG 6 wire The field lightning arrestor can be installed in a base can preferred or direct earth buried Heat shrink each L 823 connector interface using an airport approved method The field li...

Page 12: ...th ground lug Meg the field lightning arrestor at 1000 VDC for one minute Replace the field lightning arrestor if resistance is less than 2 GΩ 2 2 Introduction The Field Lightning Arrestor incorporates distribution class Metal Oxide Varistors MOVs When a voltage transient occurs the impedance of the MOVs changes from a near open circuit to a highly conductive path to ground clamping the voltage to...

Page 13: ... must meet local codes Route electrical wiring along a protected path Make sure they will not be damaged by moving equipment Protect components from damage wear and harsh environment conditions Allow ample room for maintenance panel accessibility and cover removal Protect equipment with safety devices as specified by applicable safety regulations If safety devices must be removed for installation ...

Page 14: ...nection from the airfield series circuit This could be from the L 830 isolation transformer or a splice found in the light base 3 Plug in the lightning arrestor as shown in the wiring diagram See Figure 1 and hook up label on enclosure 4 After the connection has been made reinstall heat shrink in accordance with local heat shrinking practice 5 Check site plan drawings and specifications to verify ...

Page 15: ...rrestor part AD071P01 Customer Supplied Connection 6 AWG min Counterpoise or Copper clad Ground Rod L 830 Field Lightning Arrestor Rating 5KV 20 A Part AD071P01 3 5 Equipment Specification Data Table 1 Operating Specification Model FLA Nominal Voltage 6 KV Continuous Operation Voltage 5 1 KV Duty Cycle 10 kA crest 20 current surges 40 kA crest 2 current surges 8 20 µs waveshape High Current Discha...

Page 16: ...Airfield Lighting Field Lightning Arrestor Installation 10 Copyright 2017 2018 ADB Safegate All Rights Reserved ...

Page 17: ...ting series circuit wiring or isolation transformers See FAA Advisory Circular 150 5340 26 current edition for series circuit troubleshooting guidance Note Series circuit insulation resistance is normally tested using either 500Vdc or 1000Vdc The insulation resistance of series circuits with Field Lightning Arrestors can be tested with voltages up to 5000Vac or 7070Vdc The following physical evide...

Page 18: ...resistance should be greater than 2G ohms If the resistance is less than 2G ohms replace the FLA Figure 2 FLA Field Insulation Resistance Check Megger Jumper Airfield Lighting Field Lightning Arrestor Troubleshooting 12 Copyright 2017 2018 ADB Safegate All Rights Reserved ...

Page 19: ...230 USA Contact Tel 1 614 861 1304 Fax 1 614 864 2069 Email adb sales us adbsafegate com Internet www adbsafegate com ADB Safegate Airfield Technologies Ltd China ADB Safegate China Address Unit 603 D Block CAMIC International Convention Center No 3 Hua Jia Di East road ChaoYang district Beijing 100102 P R China Contact Tel 86 10 8476 0106 Fax 86 10 8476 0090 Email china safegate com Internet www ...

Page 20: ......

Reviews: