Note
Depending on the design of the counterpoise lightning system, connecting the FLA directly to a dedicated ground
rod may provide more effective protection of the circuit.
6. After the FLA has been installed, reinstall the light fixture back onto the light base and torque the mounting bolts to the
required torque specifications found in the equipment product manual.
Figure 1: Connection Diagram
Field Circuit
Connection
(6.6 A or 20 A)
Secondary
to Airfield Light
Field Circuit
Connection
(6.6 A or 20 A)
Field Circuit
Connection
(6.6 A or 20 A)
Field Circuit
Connection
(6.6 A or 20 A)
Field Circuit
Lightning Arrestor
(part# AD071P01)
Customer Supplied
Connection #6 AWG min.
Counterpoise or
Copper-clad
Ground Rod
L-830
Field Lightning Arrestor
Rating: 5KV, 20 A
Part# AD071P01
3.5 Equipment Specification Data
Table 1: Operating Specification
Model
FLA
Nominal Voltage
6 KV
Continuous Operation Voltage
5.1 KV
Duty Cycle
10 kA crest (20 current surges)
40 kA crest (2 current surges)
8 / 20 µs waveshape
High Current Discharge (Short Duration)
100 kA crest (2 current surges)
4 / 10 µs waveshape
Low Current Discharge (Long Duration)
250A crest (20 current surges) 2000 µs duration
Maximum Discharge Voltage
19.8kV Crest @ 10kA, 24.7KV Crest @ 40kA 8 / 20 µs waveshape
Protection Index
IP68 (NEMA 6P)
Operating Temperature
-40°F to +140°F (-40°C to +60°C)
Weight
2 kg (4.4 lb)
96A0489, Rev. B, 2018/03/06
9
Copyright
©
2017–2018 ADB Safegate, All Rights Reserved