EURODIM TWIN TECH
Page
34
sur
92
7.3.1
Module identification
All the modules are fitted with an EEPROM cue, which contains an ID code. When the modules are installed
in the cabinet, this ID is communicated to the controller.
This information is available in the "Present" column.
In this column, the following information can be obtained: a correct ID or "Undefined slot" for a module
that is unidentified by the controller or uninstalled.
EURODIM TWIN TECH module identification table
In the Reference column, we are given the type of module that will actually be used by the controller to
control the circuits. This reference may be modified manually. If a position in the cabinet is not used, the
user must fill it in as an "undefined slot".
Use the wheel to view the ID of each module.
TD4x3/MN/1R
T
ECHNOLOGY:
S (sinewave - standard with diagnostics only with 4R)
T (thyristor dimmer with 400µS rise time)
P (thyristor dimmer with 200µS rise time)
F (Fluo dimmer with 200µS and remote controlled preheat)
R (DimSwitch with 200µS rise time)
H(DimSwitch with dual 0µS/400µS rise time-standard with
diagnostics)
N (Non-Dim no remote control)
D (Full diagnostic version - optional)
Number of circuits in the module
Rated Load in kW of each circuit in the module
MN (MCB with 1P+N protection)
RCD protection:
No RCD
1R (per module)
2R (2 individual protections - Fluo)
3R (3 individual protections)
4R (4 individual protections)