EURODIM TWIN TECH
Page
71
sur
92
•
if the load > 5.5.5KW (for a 5kW module)
•
if the load is > 11KW (for a 10kW module)
3 -
Displays "
NO
" in all other cases
OverCurrent
(per circuit)
Sinewave:
•
Displays
“low”: if the current is > 13
A
•
Displays "average": if the current is > 16 A
•
Displays "Severe": if the current is > 20 A
Thyristor with diag.: always "
N/A
"
Short-circuit
(per circuit)
Sinewave:
Displays "
NO
"
Displays "
YES
":
•
The control is automatically set to zero
•
After 2 mins, an actual control test is repeated and if the overload is "severe"
again, a second test is conducted. If the overload is still
severe
, a status
message is displayed at the bottom of the screen, requesting the user to set
all the DMX/ARTNET inputs of the circuit to zero for 30 secs.
Thyristor with diag.: always
N/A
Temperature
Sinewave:
1 -
Displays "
OK
"
2 -
Displays “
too high
” => automatic contro
l reduction until the temperature
now longer exceeds the threshold set
Note
: The measure be different between the ½ circuits and the ¾ circuits
Thyristor with diag.: always
N/A
Main voltage
Sinewave:
1 -
Displays "
OK
"
Cases 2 and 3 do not trigger a module error as it is the main voltage that is
incorrect
2 -
Displays "
Too high
"
3 -
Displays “
too low
”