150-504-100-03
Installation
HRE-504 List 1, List 1B, and List 2
August 1, 2002
13
6
Use 6 AWG cable to connect the main cable shield to the ground rod.
7
If commercial power ground exists, bond telephone ground to power ground as a safety measure.
8
Use a Megger-type ohmmeter to measure the main cable shield resistance to ground rods. The resistance must
be 5
W
or less.
9
If the resistance requirement in
is not met, ground the main cable shield every 2,000 feet (610 m).
Figure 5.
Grounding for Pole Mounted Unit
If the main feeder cable’s shield is bonded to the stub’s shield, the green insulated or bonded
stub shield wire should be disconnected from the metal card cage base. This is recommended
to reduce service affecting noise from being injected into the doubler circuits from circulating
ground loop currents and help inhibit corrosion.
HRE-504
No. 6 Gauge Wire
Grounding
Lug
Ground
Rods
No. 6 Gauge Wire
Bullet Bond
Field Side
CO Side
Splice Case
5 ft (1.52 m) Typical
Stub