8
American Dryer Corp.
113279 - 9
Installation Procedures ______________
Installation should be performed by competent professional
in accordance with local, state, and country codes. In the
absence of these codes, the installation must conform to
applicable American National Standards: National Fuel Gas
Code ANSI Z223.1/NFPA 54 and National Electric Code ANSI/
NFPA 70, or in Canada, the installation must conform to
applicable Canadian Standards: Natural Gas and Propane
Installation Code CSA B149.1 and Canadian Electric Code
CSA C22.1.
Location Requirements ______________
Before installing the dryer, ensure the location conforms to
local codes and ordinances. In the absence of such codes
or ordinances the location must conform with National Fuel
Gas Code ANSI Z223.1/NFPA 54, or in Canada, the
installation must conform to applicable Canadian Standards:
Natural Gas and Propane Installation Code CSA B149.1.
The dryer must be installed on a sound level floor capable of
supporting its weight. Carpeting must be removed from the
floor area that the dryer is to rest on.
The dryer must not be installed or stored in an area where it
will be exposed to water and/or weather.
Dryers installed in residential garages must be elevated
18-inches (45.72 cm) above the floor.
Provisions for adequate air supply must be provided as noted
in this manual (refer to Fresh Air Supply Requirements
section).
Clearance provisions must be made from combustible
construction as noted in this manual (refer to Dryer Enclosure
Requirements section).
Provisions must be made for adequate clearances for
servicing and for operation as noted in this manual (refer to
Dryer Enclosure Requirements section).
The dryer must be installed with a proper exhaust duct
connection to the outside as noted in this manual (refer to
Exhaust Requirements section).
The dryer must be located in an area where correct exhaust
venting can be achieved as noted in this manual (refer to
Exhaust Requirements section).
IMPORTANT: The dryer should be located where a
minimum amount of exhaust ducting will be necessary.
The dryer must be installed with adequate clearance for air
openings into the combustion chamber.
CAUTION: This dryer produces combustible lint and
must be exhausted to the outdoors. Every 6 months,
inspect the exhaust ducting and remove any lint
buildup.
IMPORTANT: The dryer must be installed in a location/
environment, which the ambient temperature remains
between 40° F (4.44° C) and 130° F (54.44° C).
A
The requirement to allow the door to open completely is
28-inches (71.12 cm).
B
A minimum overhead clearance of 6-inches (15.24 cm)
is required.
C
Dryer should be positioned a minimum of 12-inches
(30.48 cm) away from the nearest obstruction. 24-inches
(60.96 cm) is recommended for ease of installation,
maintenance, and service.
D
1/16” (1.5875 mm) minimum is required.
E
Flooring should be level and below dryer cabinet for ease
of removing panels during maintenance.
F
Dryers may be positioned sidewall to sidewall, however
a 1/16” (1.5875 mm) minimum allowance must be made
for the opening and closing of the control door, along
with the removal of panels during maintenance.
Unpacking / Setting Up ________________
Remove protective shipping material (i.e., plastic wrap and
optional shipping box) from the dryer.
IMPORTANT: Dryer must be transported and handled in an
upright position at all times.
The dryer can be moved to its final location while still attached
to the skid or with the skid removed.
With the skid removed, use caution and assure all four
leveling legs are fully retracted, if the dryer is to be slid into
its final position.
Leveling Dryer
The dryer is equipped with four leveling legs, one at each
corner of the base. For optimum performance the dryer
should be level front-to-back and side-to-side.
Dryer Enclosure Requirements _______
Commercial Type II
Bulkheads and partitions should be made of noncombustible
material.
NOTE: Allowances must be made for opening the control
door.
Summary of Contents for AD22
Page 22: ...ADC Part No 113279 9 06 16 22 ...