ADCP-80-353 • Issue 2 • August 2002 • Section 2: Installation
Page 2-10
©
2002, ADC Telecommunications, Inc.
Figure 2-8. Recommended Cross-Connect Routing
9202-A
RECOMMENDED SPACING
UPPER
CROSS-
CONNECT
WIREWAYS
CROSS-
CONNECT
JUMPER
VERTICAL
CROSS-
CONNECT
WIREWAYS
LOWER
CROSS-
CONNECT
WIREWAYS
NOTE: BASED ON THE TYPE OF CABLE SELECTED FOR EQUIPMENT IN/OUT CABLING AND CROSS-CONNECT JUMPER,
THE ADC RECOMMENDED SPACING IS AS FOLLOWS:
APPLICATION
EQUIPMENT I/O
X-CONN
SPACERS REQUIRED FOR UEF BAYS
735A/734A
735A OR RG59
ONE 10-INCH (25.4 CM) BETWEEN BAYS
WITH ONE 5-INCH (12.7 CM) ON THE ENDS
ROUTING RULES
A. All jumpers in the left-hand side of the cross-connect field should enter and leave the bay from the left vertical wireways.
B. All jumpers in the right-hand side of the cross-connect field should enter and leave the bay from the right vertical wireways.
C. All intrabay cross-connects should use the vertical rings except when terminations are in the same panel.
D. All interbay cross-connects should use the horizontal wireways.
E. All jumpers originating in the upper half of the cross-connect field should route via the upper horizontal wireways.
F. All jumpers originating in the lower half of the cross-connect field should route via the lower horizontal wireways.
G. Whenever a jumper changes direction, it should do so at a ring or wireway.