SCP-FCS717-022-03H
Installation and Test
FCS-717 List 2B
January 6, 2003
13
Connect the CO Battery
The FCS-717 List 2B COT shelf can be powered from a single battery feed or from a split battery feed.
Single Battery Feed.
For a single battery feed do the following (see
1
Connect the wire from CO battery A to TB1 (-48V_A) termination point.
2
Connect the wire from CO battery return to TB4 (RTN_A) termination point.
3
Connect the CO battery wires from TB1 (-48V_A) on the COT shelf to the equipment bay fuse panel
termination points.
Figure 5.
Connecting a Single Battery Feed
Use 12 AWG or larger wire (or multiple wires of a smaller gauge) to ensure good power
connections to the PG-Flex system.
When the FCS-717 List 2B COT shelf is configured for a single battery feed, insert a 10 amp
fuse into the equipment bay fuse panel where the PG-Flex CO battery wire is terminated.
TB4
RTN_A
CO Battery Return
CO Battery A
Equipment Bay
Fuse Panel
TB3
RTN_B
TB1
-48V_A
TB2
-48V_B
Jumper (installed)
10 AMP