FSU-571 System Controller Card – Quick Installation Guide
Page 1 of 2
The ADC
®
PG-Flex
Plus
System Controller Card manages DS0
cross-connections between T1 interface cards in the Universal
Access Platform (UAP) system.
R
EQUIRED
E
QUIPMENT
• anti-static wrist strap
• flat-head screwdriver
I
NSTALLING
THE
S
YSTEM
C
ONTROLLER
C
ARD
The System Controller Cards can only be installed in slots 11 and
12 of the Universal Access Platform (UAP) system.
1. Put on an anti-static wrist strap and plug it into an ESD
grounding jack on the UAP chassis. See Operating Company
practices for ESD grounding locations.
2. Remove the System Controller Card’s slot cover(s) from the
slot in which you want to install the card.
a. Loosen the thumbscrews at the top and bottom of the slot
covers.
b. Remove the slot covers.
3. Open the retaining latch on the front of the card.
4. Align the card with the card guide and carefully slide it into
the slot.
5. Simultaneously close the top and bottom ejector levers to
install the card in the slot.
6. Secure the card in the chassis by tightening the thumbscrews
with a flat-head screwdriver.
S
YSTEM
C
ONTROLLER
C
ARD
LED
S
The System Controller Card LEDs on the front of the active sys-
tem controller card indicate the overall status of the UAP. The
following table describes the system controller card LEDs. See
the figure left for location of the system controller card LEDs.
If not installing a redundant sytem controller card, the sin-
gle system controller card must be installed in slot 11.
Fail
Active
Critical
Major
Minor
Misc
ACO
ACO
Button
Craft port
(DB-9 connector)
Status
LEDs
LED
Color
State
Description
FAIL
Red
Off
No failures exist on the system
controller card.
On
At least one card failure exists on
the system controller card.
ACT
Green
Off
The system controller card is not
active.
On
The system controller card is
active.
CRIT
Red
Off
No outstanding critical alarms exist
in the UAP.
On
At least one outstanding critical
alarm exists in the UAP.
MAJ
Red
Off
No outstanding major alarms exist
in the UAP.
On
At least one outstanding major
alarm exists in the UAP.
MIN
Yellow
Off
No outstanding minor alarms exist
in the UAP.
On
At least one outstanding minor
alarm exists in the UAP.
MISC
Yellow
Off
No outstanding miscellaneous
alarms exist in the UAP.
Miscellaneous alarms pertain to
power and fan problems and user-
configured external alarms.
On
At least one outstanding
miscellaneous alarm exists in the
UAP.
ACO
Green
Off
No alarm condition exists or the
Alarm Cut-OFF (ACO) button has
not been pressed during a current
alarm condition.
On
The ACO cutoff button has been
pressed during an alarm condition;
LED remains green until there is a
status change in the critical, major,
or minor alarm.