Using
terminal commands
R
EMOTE
Yes, SET only.
E
XAMPLE
PMP 65 72
9193 PMP 0
#
PMP
9193 PMP 65 72 0
#
ANLG
A
VAILABLE FOR
A731
A733
A732
A733GSM
D
ESCRIPTION
Sets/returns various parameters of the analog subsystem (for example, the
sampling/averaging method used for individual data acquisition channels).
P
ARAMETERS
A control byte specifying the command and the analog input channel number the
command is acting on:
Command Code
Channel Number
Fig. 14:
The ANLG Control Byte Layout.
Some commands may also require one or two additional 12-bit parameters
representing threshold values.
•
The Channel Number selects the analog channel that will be affected by
the command. For the A733, only 0000 to 1011 are accepted (only 12
analog channels are available).
•
The Command Code specifies the operation that will be applied to the
selected channel. They are described in Table below.
Code Description
Parameters
Returns
0000 RSM – Read Sampling Method.
This command reads the current
programmed sampling method
for all analog input channels.
None
The current
sampling methods
and the result (OK
or ERROR); see
also the sampling
table below
0001 SSMMI – Set Sampling Method
to Minimum. The specified
analog channel is instructed to
store the lowest sampled value.
The channel num-
ber
Result (OK or
ERROR)
0010 SSMMA – Set Sampling Method
to Maximum. The specified
analog channel is instructed to
store the highest sampled value.
The channel num-
ber
Result (OK or
ERROR)
0011 SSMS – Set Sampling Method to
Sum. The specified analog
channel is instructed to store the
sum of all sampled values.
The channel num-
ber
Result (OK or
ERROR)
0100 SSMAA – Set Sampling Method
to Arithmetic Average. The
specified analog channel is
The channel num-
ber
Result (OK or
ERROR)
32