PA 358
Technical description Chapter 8
30
The outputs are set to the following output value after a reset in bipolar mode:
Output range
Output set to
0-10V 5V
0-5V 2,5V
±10V 0V
±5V 0V
0-20mA 10mA
4-20mA 12mA
8.5
Adjustment of the current output channels
If you use the current outputs, you can adjust them.
To this purpose, each output has been equipped with two potentiometers.
•
One for the GAIN adjustment at 0-20 mA / 4-20 mA
•
One for the OFFSET adjustment at 4 mA
Table 8-2: Potentiometers for adjusting the current output channels
Channel
Offset
Gain
0 P1 P2
1 P3 P4
2 P5 P6
3 P7 P8
4 P9 P10
5 P11 P12
6 P13 P14
7 P15 P16