Mounting and connection
MSX-ilog-xx-xx
www.addi-data.com
27
ADDI-DATA
®
PARTNER FÜR PRÄZISION
3.4.2 “Status” LED
The “Status” LED provides information on the current operating state of your MSX-ilog data logger.
Table 3-9: “Status” LED
Display
Meaning
Possible cause
Recommendation
No display
The data logger is
switched off.
Connect the data logger to the
supply voltage.
Lights green
The data logger is
ready for
operation.
Flashes green
The data logger is
working.
- A firmware update is
being applied.
- Data acquisition is in
progress.
Flashes
yellow/green
Data acquisition is
possible, but some
components are not
working correctly.
- The flash memory is
no longer working
properly.
- An attempt has been
made to configure
the data logger with
an incorrect IP
address.
- Check your IP address.
- Contact us for a replacement or
repair.
Lights yellow
The data logger is
operational but
cannot be accessed
via the network.
- The data logger is
booting up.
- The network cables
are not connected.
- Wait until the data logger
initialisation has been
completed (approx. 40 seconds).
- Check the Ethernet connection
(see LEDs “Port 0 ACT/LINK”
and “Port 1 ACT/LINK”).
Flashes yellow
Data acquisition is
not possible, but
the data logger can
be accessed via the
network
connection.
- An update has been
applied with faulty
firmware.
- A major component
is not working
correctly.
- There has been a
short circuit on the
primary side of one
or more sensors.
- Check the diagnosis on the web
interface of the data logger.
- Check the cables and sensors
connected to the Ethernet data
logger. Use the latest firmware
for your data logger.
- Contact us for a replacement or