Web interface: Quick access to the Ethernet data logger
MSX-ilog-xx-xx
www.addi-data.com
33
ADDI-DATA
®
PARTNER FÜR PRÄZISION
4.3 Menu item “Acquisition”
4.3.1 “Channel configuration” tab
Fig. 4-3: Acquisition: Channel configuration (master system)
On this tab, you can configure the channels of your MSX-ilog data logger. For each channel, you can
set the following parameters:
•
Select:
You can select the channels you want to acquire.
•
Colour:
Each channel can be assigned a colour. This colour is used for the visualisation of the
channel.
•
Identifier:
It is possible to define a name for each channel, such as “Transducer1”, “Pt100_1”, etc.
This name helps to identify the channel when it is visualised.
•
Unit:
In this field, you can enter the desired unit for each channel.
•
Frequency (Hz):
You can select the frequency at which each channel should be acquired.
It is not necessary to set the same frequency for each channel. For example, channel 1 can be
acquired at 100 Hz and channel 2 at 500 Hz at the same time.
•
Offset:
You can specify an offset for each channel. This value is added to the real value of the
respective channel.
•
Multiplier:
For each channel, a multiplication factor can be specified. The real value of the
channel is multiplied by this factor. If you enter both an offset and a multiplication factor, the first
operation will be the multiplication and the second one the addition of the offset.
•
Gain:
The measurement gain for each channel can be selected.
•
Polarity:
The channels can be acquired in bipolar or unipolar mode.
NOTICE!
After setting all parameters, you have to click on the
“Save configuration” button above.