background image

 

 

   

     

    

 Pa

ge

 7

 -

 Ch

ap

te

r:

 

Ba

tt

er

C

ar

Completely  automatic,  all  devices  are  suitable  to  charge  most  batteries types thank  to  User  Selectable 
charging curves. They can charge open lead acid, sealed lead acid, Gel, Ni-Cd and Li-Ion. It is possible to 
change or add other charging curves connecting the device to a portable PC. 
Caution: Switch off the system before Setting the jumper. Only jumper in position 6 is Refreshed also with 
power ON. 

 

 

 

Battery Type Selection (Only for CBI485A and CBI485A/S) 

 

 

 

Jumper 
Position 
(Size 1) 

Jumper Position  
(Size 2) 

Jumper Position 
(Size 3) 

Dip Switch 
Position 
(Size 4) 

Float charge 

(Volt/Cell) 

Fast charge 

(Volt/Cell) 

Open Lead   

 

 

 

2.23 

2.40 

AGM Low    

 

 

 

2.25 

2.40 

AGM High   

 

 

 

2.27 

2.40 

Gel Battery   

 

 

 

2.30 

2.40 

Battery Type chemistry Selection 

 

 

 

Jumper 
Position 
(Size 1) 

Jumper 
Position 
(Size 2) 

Jumper Position 
(Size 3) 

Dip 
Switch 
Position 
(Size 4) 

Float charge 

(Volt/Cell)

 

Fast charge 

(Volt/Cell)

 

Open Lead  

 

 

 

 

2.23 

2.40 

(AGM) Low 

 

 

 

 

2.25 

2.40 

Gel Battery 

 

 

 

 

2.30 

2.40 

NiCd  

 

 

 

 

1.4V/cell 

(12V:10 cells) 
(24V:20 cells) 
(48V:40 cells)

 

1.5V/cell 

(12V:10 cells) 
(24V:20 cells) 
(48V:40 cells) 

Li-Ion (4)  

 

 

 

 

3.45 

(12V:4 cells) 
(24V:8 cells) 

3.65 

(12V:4 cells) 
(24V:8 cells) 

Config Mode (5)   

 

 

 

Configure by DPY351 or 
ADELVIEWSsystem. 

Functional Setting  

Function 

Battery Life test 

ON 

 

 

 

 

Jumper present or dip 
switch ON: Life test enabled 
(not for NiCd) 

Boost - Fast 

Charge Enable 

(3) 

 

 

 

 

Jumper present: Fast 
Charge enabled. It is 
possible remote Fast 
Charge enabling by 
RTCONN cable 

“Start from 

Battery” (without 

Input Mains) (1) 

 

 

 

 

Switch ON the system 
without the “Mains In Vac”, 
only the battery is 
connected. For connection 
to external Push button use 
RTCONN cable 

UPS Disabling 

(2)    

 

 

 
 

 

If jumper removed: UPS 
function disabled 
Use RTCONN cable for 
connection to external 
Contact.  

Summary of Contents for ALL IN ONE CBI Series

Page 1: ...y efficiency reduces risk of battery damage and allows a safe operation in permanent connection Predefined curves can be selected by jumpers or DIP switch to optimize the charge of different battery t...

Page 2: ...or Load DC Bus one Input Output for connection to the battery N 1 battery 12 Vdc for CBI 12xx N 2 battery 12 Vdc connected in Series for CBI 24xx N 4 battery 12 Vdc connected in Series for CBI 48xx 5...

Page 3: ...installation clearance of 10 mm left right between two power supplies and avoid installing the power supplies on top of each other Note Avoid return voltage e g from a decelerating motor or battery w...

Page 4: ...45 min 20 h Load 12 A No 3 min 12 min 30 min 600 min Load 15 A No No 9 min 20 min 400 min Load 20 A No No 7 min 13 min 240 min 6 LAY OUT AND CONNECTIONS 7 INPUT AND OUTPUT LOAD AND BATTERY CONNECTION...

Page 5: ...wer 2 See Diagnosis Led 8 1 4 Relay Contact Rating Max DC1 30 Vdc 1 A AC1 60 Vac 1A Resistive load EN 60947 4 1 Min 1mA at 5 Vdc Min permissive load 8 1 5 Charging Mode STATUS Status Led Diagnosis No...

Page 6: ...Acid Gel Ni Cd option They guarantee battery reliability in time by continuously testing the internal impedance status avoids any possible risk of damages and grants a permanent reliable and safe conn...

Page 7: ...er Position Size 1 Jumper Position Size 2 Jumper Position Size 3 Dip Switch Position Size 4 Float charge Volt Cell Fast charge Volt Cell Open Lead 2 23 2 40 AGM Low 2 25 2 40 Gel Battery 2 30 2 40 NiC...

Page 8: ...he quality resistance on the battery connection is checked every 60 sec This to detect if the cable connection has been properly made Battery in Open Circuit or Sulphated In Float charging mode the Al...

Page 9: ...STICS The unit is a SLAVE in a MODBUS network The slave units are compliant to the following specifications Transmission mode MODBUS RTU Electrical Interface RS485 half duplex serial line Baud rate 48...

Page 10: ...onnection Diagram Size3 CBI500 DPYCONN500 is a special cable for the connection of CBI Size3 and the other device max leght 0 5m RJ45COUPLER is e T connection RJ45 for daisy Chain with CBI Size3 RJCON...

Page 11: ...ections to the external device like RTU PC DPY351 For the connection to RTU PLC or similar devices refer to the instruction manuals Modbus specifications_R14 Web Site www adelsystem com For configurat...

Page 12: ...ity to EN60950 UL60950 1 and CSA C22 2 No 60950 1 07 Information Technology Equipment Safety Part1 General Requirement Device is intended to be installed in a cabinet protected from external shocks or...

Reviews: