background image

 
 

Instruction Manual DPY351_R11 

Page 2 

Safety and warning notes 

WARNING 

–  Explosion  Hazard  Do  not  disconnect  Equipment 

unless power has been switched off or the area is known to be non-
hazardous. 

WARNING 

– Explosion  Hazard. Substitution of components may 

impair suitability for class I, Division 2. 

WARNING 

– Switch off the system before connecting the module. Never work 

on  the  machine  when  it  is  live.  The  device  must  be  installed  in  according  to 
EN61010  or  EN62368-1.  The  device  must  have  a  suitable  isolating  facility 
outside the power supply unit, via which can be switched to idle. Danger of fatal 
Injury! 

WARNING 

– The device is equipped whit an internal fuse. If the internal fuse 

blow Up (fails opens), it is most probable that there is a fault in the device. If this 
failure occurs, the device must be returned to the factory. 

How to Install  

2.1  Dimensions 

 

Fig. 1 – Dimensional drawing of the DPY351 

2.2  Panel Mounting 

Fig. 1 shows a dimensional drawing of the DPY351 .It is possible to mount the 
DPY351 through a 90mm hole on the panel and fix it by 4 screws 2.9x16. There 
is  no  limit  for  the  Panel  thickness.  A  mounting  template  at  the  end  of  this 
instruction manual is provided. 
Note: In conditions of extremely vibrations, mount the device on suitable anti-
vibration mounting. 

2.3 

How to Supply DPY351 

The DPY351 can be powered  from the ADELBus  network. There must  be  an 
ADELBus (AUX3) powering devices available to provide sufficient power to the 
network. If there is no ADELBus powering device or the available power is not 
sufficient,  the  DPY351  must  be  connected  to  a  12/24/48  V  battery  or  Output 
Load via the supplied connector (AUX5).

 

2.4  Device Connection (Fig.2) 

 

Fig. 2 – Connections to the DPY351 rear panel 

Reference 

Description 

Temperature Probe (AUX1) 

Ethernet (AUX2) 

ADELBus: CANBUS, ModBus (AUX3) 

USB (AUX4) 

Auxiliary Power, I/O port (AUX5) 

Dip-switches (Hardware Config

(AUX6) 

2.4.1 

Auxiliary temperature sensor (AUX1) 

Auxiliary temperature sensor connection 

(RJtemp accessory probe)

 to measure 

the environmental temperature where needed. 

2.4.2 

Ethernet Connection (AUX2) 

"HUB" collector function of the connected devices to the ADELBus network, to 
transport  via  Ethernet.  The  available  protocols  are  the  Modbus  TCP/IP,  the 
SNMP protocol and the MQTTs. An internal password-protected HTTP server 
allows to configure the network connection, to enable the network protocols, to 
remotely control the DPY351 and to download the data log and event log. 

2.4.3 

PowerBus Connection (AUX3) 

Automated  RJ45  cable  connection  for  Modbus  and  CANBUS  protocols.  The 
Display must be powered via the AUX5 connector if the power provided from a 
power device connected to AUX3 is not enough. 

2.4.4 

USB Connection (AUX4) 

USB Connection for software updates via PC. 

2.4.5 

Auxiliary Input Power (AUX5) 

Connect  the positive wire to terminal 1, the negative  wire to terminal  2 of the 
connector a 3mm flat blade screw driver to push in the Spring Connect to supply 
the DPY351 from a CBI Size3, it is necessary to connect the Output Load + and 
–  to  Aux  5  since  these  devices  cannot  provide  power  through  the  AUX3 
connector 

 

Fig. 3 – AUX 5 connector pinout 

2.4.6 

Input / Output State Terminal 3,4,7,8 (AUX5) 

The device is equipped with two digital inputs (terminal 3,4) suitable to reading 
external conditions. They can be used for the most various  
checks. For example: the control of opening doors, presence of protective earth, 
verification of presence of Light, gas, pressure, etc...  
The two inputs can accept any voltage between 0 and 70V with respect to the 
DPY351 ground reference (AUX5, pin 2). Voltages lower than 3V are read as a 
“0” or “logic-low” level; voltages higher than 7V are read as “1” or “logic-high” 
level. A logic-high or logic-low level on either input can be configured to trigger 
an  alarm:  to  perform  such  configuration  the 

Menu  >  Display  Configuration  > 

Advanced Configuration > Input/output > Input

 menu page must be accessed. 

It is then possible to configure, separately for each of the two inputs, which logic 
level should trigger an alarm, if enabled, or no-alarm. 
The Output relay (terminal 7,8) can be activated according to the  state of the 
inputs by means of an  “Event” function or when the environmental temperature 
measured  by  the  sensor  connected  to  AUX1  is  higher  or  lower  than  user-
configurable alarm thresholds, or when any alarm is standing. The configuration 
of  the  output  relay  behavior  can  be  done  at  the  page

  Menu  >  Display 

Configuration > Advanced Configuration > Input/Output > Output (relay), 

where 

it can be configured to be always open, always close, close when there is an 
alarm  on  the  inputs,  close  when  there  is  an  alarm  on  the  environmental 
temperature (or both), on alarms or on notifications. 
- Output Relay Free Switch Contact (NO) 

Max. current that can be switched (EN60947.4.1): 
Max. DC1: 30 Vdc 1 A; AC1: 60 Vac 1A    
Min.1mA at 5 Vdc (Min Resistive load)  

2.4.7 

How to connect the shunt in CBI Size 3  

To display the load current on CBI “SIZE 3” it is necessary to add an external 
shunt device, as explained in Fig.4. Consequently, it is possible to add this 
parameter on the Dashboard or the monitoring panel. The supported shunt 
ratings are 75mV/30A and 75mV/50A. 

Fig. 4 – External Shunt connection for CBI Size 3 

Shunt must be installed low-side in series between the Output Load -  of the CBI 
Size 3 and the “negative” of the load.  

CAUTION

: NEVER install the shunt in series with the high-side of the load or 

the battery! There is the risk of damaging the DPY351. Any damage resulting 
from such wiring will void the warranty. 
CAUTION: NEVER connect the CBI Load or battery outputs across the Shunt+ 
and Shunt- inputs of the DPY351! There is the risk of damaging the DPY351. 
Any damage resulting from such wiring will void the warranty. 
In  order  to  get  accurate  measurements  from  the  external  shunt,  the  correct 
shunt rating must be configured on the DPY351. This can be done in the 

Menu 

>  Display  Configuration  >  Advanced  Configuration  >  Input/output  >  External 
shunt sensor

 menu. In the Sensor type page it is possible to select the shunt 

rating. The setting done in this page must match the rating of the installed shunt. 
In  the  Sensor  calibration  page  it  is  possible  to  perform  a  one-  or  two-point 
calibration to improve the measurement accuracy in the end-application. With a 
single-point  calibration  only  the  zero-current  calibration  is  performed.  With  a 
two-point  calibration  both  the  offset  and  gain  calibration  is  performed.  In  the 
latter case the display prompts the user to specify the reference current provided 
so that the DPY351 can compute the correct calibration constants. The Sensor 
calibration is managed as a wizard that guides the user through the calibration 
process. It is also possible to set a high-current alarm threshold. If such current 
magnitude  is  exceeded,  an  alarm  is  triggered  which,  in  turn,  can  be  used  to 
activate the output relay, if its setting is “Close on alarm”. 

2.4.8 

Cabel Connections (AUX5) 

Use appropriate wire size to connect the AUX5 power supply to the 
battery. Fuse: Insert a 1A fuse in the positive battery line. For cable 
size see Technical Data section. 

1

2

3

4

5

6

C

a

 

Reviews: