CONTROL PANEL

RPM

INPUT POLLING LOOP

EXTENSION POLLING LOOP

RPM

4297

RPM

RPM

NOTE:  4297 DRAWS AC CURRENT

FROM INPUT POLLING LOOP.

TO

OTHER

RPMS

INPUT LOOP LIMITS:

REFER TO THE CONTROL PANELÕS INSTALLATION
INSTRUCTIONS FOR LIMITS ON MAX CURRENT DRAW,
MAX NUMBER OF DEVICES, MAX INDIVIDUAL WIRE RUN
LENGTH, AND MAX COMBINED WIRE RUN LENGTH.

EXTENSION POLLING LOOP LIMITS:

¥  128 mA MAX. LIMIT CURRENT TO 64 mA ON ANY

INDIVIDUAL WIRE RUN.

¥  NO MORE THAN 64 DEVICES MAY BE USED.
¥  NO INDIVIDUAL WIRE RUN CAN EXCEED:

¥  TOTAL LENGTH OF ALL WIRE RUNS COMBINED CANNOT

EXCEED 4000 FT. (2000 FT. IF USING UNSHIELDED WIRE

GAUGE    LENGTH

#22        100 FT

#20        150 FT

#18        225 FT

#16        375 FT

COMBINED INPUT AND EXTENSION LOOP LIMITS:

¥  NO MORE THAN 64 DEVICES COMBINED.
¥  TOTAL LENGTH OF ALL WIRE RUNS ON BOTH LOOPS

COMBINED CANNOT EXCEED 5200 FT. (2600 FT. IF
USING UNSHIELDED WIRE IN CONDUIT, OR IF USING
SHIELDED WIRE).

NOTE:

SOME CONTROL PANELS MAY ALLOW THESE

LIMITS TO BE EXCEEDED. REFER TO THE CONTROL

Figure 4.  Polling Loop Connections Using One 4297 Module

CONTROL PANEL

EXTENSION POLLING LOOP #1

4297

RPM

INPUT LOOP LIMITS:

REFER TO THE CONTROL PANELÕS
INSTALLATION INSTRUCTIONS.

COMBINED INPUT AND EXTENSION LOOP LIMITS:

¥  NO MORE THAN 64 DEVICES COMBINED ON THE INPUT LOOP AND EXTENSION

LOOP #1. NO MORE THAN 64 DEVICES COMBINED ON THE INPUT LOOP AND 
EXTENSION LOOP #2.

¥  TOTAL LENGTH OF ALL WIRE RUNS ON THE INPUT LOOP AND EXTENSION LOOP #1

COMBINED CANNOT EXCEED 5200 FT. (2600 FT. IF USING UNSHIELDED WIRE IN
CONDUIT, OR SHIELDED WIRE). TOTAL LENGTH OF ALL WIRE RUNS ON THE INPUT
LOOP AND EXTENSION LOOP #2 COMBINED CANNOT EXCEED 5200 FT. (2600 FT. IF
USING UNSHIELDED WIRE IN CONDUIT, OR SHIELDED WIRE).

NOTE:

SOME CONTROL PANELS MAY ALLOW THESE LIMITS TO BE EXCEEDED. REFER

TO THE CONTROL PANELÕS INSTALLATION INSTRUCTIONS.

4297

RPM

EXTENSION POLLING LOOP #2

INPUT POLLING LOOP

EXTENSION POLLING LOOP LIMITS:
REFER TO FIGURE 4.

EXTENSION POLLING LOOP LIMITS:
REFER TO FIGURE 4.

¥ DO NOT CONNECT 4297 MODULES IN

SERIES (i.e., DO NOT CONNECT ONE
MODULEÕS EXTENSION LOOP TO
ANOTHER MODULEÕS INPUT LOOP.)

¥ DO NOT CONNECT MORE THAN TWO

4297 MODULES IN PARALLEL.

Figure 5.  Polling Loop Connections Using Two 4297 Modules

SPECIFICATIONS 

ÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐÐ

Physical:
6-7/16"W x 4-1/4"H x 1-1/4"D (163mm x 108mm x 32mm)

Electrical:

12V Input Rating:

Input Voltage: 12VDC (10VDC - 14VDC)
Input Current: 50MA + extension loop drain (128MA max) 

during normal operation. Increases to 350MA
when extension loop shorted.

12V Battery Rating:

Battery Type:

12V, 1.2AH min/2.6AH max lead-acid 
battery. Use gel type lead-acid battery

Float Voltage:

13.65VDC

Standby Time:

Exceeds 4 hrs with 1.2AH or larger battery

Recharge Time: Up to 48 hours
Miscellaneous:

PTC thermistor provides reverse battery
connection  protection

Extension Polling Loop Rating:

Output Current:

128MA max. Do not draw more than 

64MA on any individual extension loop 
wire run.

Miscellaneous:

Refer to Figures 4, 5 for limits on polling 
loop wire run length. The extension loop is 
power limited.

Regulatory Agency Listing
UL 609
 commercial burglary,  UL864 commercial fire,  UL985
household fire and  UL1023 household burglary.