– 2 –
SETTING THE SITE ID
Some ADEMCO wireless devices (e.g., 5827, 5804BD) use a
programmed house ID to help avoid communication conflicts with
nearby installations. The 5800RP automatically passes all house
ID information to the appropriate receiver.
Certain newer ADEMCO wireless devices, such as the 5883 and
the 5839, use a “Site ID” instead of a House ID. The Site ID is a
factory-assigned, unique serial number built into each 5883
transceiver and must be entered into each device that uses it. The
Site ID provides many more combinations than a House ID, and
therefore is less likely to have conflicts with nearby installations.
When using the 5800RP with wireless devices that use a Site ID,
follow the steps below to enter a permanent copy of the Site ID in
the 5800RP. This procedure assumes that all such devices have
been successfully set-up and tested with the 5883, although they
may not yet be mounted in their final locations.
1.
Put the control (and the 5883) in the Go/No Go Test mode.
2.
Remove the 5800RP's cover by inserting and twisting a
screwdriver blade in the slot at the center of the cover's lower
edge. Note that removing the cover also places the 5800RP in
the Go/No Go Test mode. This decreases its range during
installation to insure an adequate margin during normal
operation.
3.
Temporarily disconnect the power supply and battery from
the 5800RP. Refer to Figure 2.
4.
Place DIP switch 1 in the ON position.
5.
Reconnect the power supply to the 5800RP. Observe that the
red LED on the 5800RP turns on and remains on. This
indicates that the 5800RP is ready to set the Site ID.
6.
Push and release the tamper switch on the 5800RP. This
causes a set-up request message to be sent to the 5883.
7.
Observe that the red LED turns off, indicating that the Site
ID has been saved in the 5800RP. If not, repeat the previous
step until it does.
NOTE: If the tamper switch is not pushed for 1 minute or if
DIP switch 1 is turned off, the red LED turns off. This
indicates the 5800RP will no longer accept the Site ID.
8.
Place DIP switch 1 in the OFF position.
9.
Replace the cover on the 5800RP.
10.
Take the control out of the Go/No Go Test mode.
11.
If needed locate the other wireless devices in their final
locations.
12.
Test all wireless devices.
ON
2
3
4
5
6
7
8
1
MUST BE OFF
FOR NON - UL;
MUST BE ON
FOR UL
3 - 8
NOT USED
MUST BE OFF
SW-1
USED WHEN
ENROLLING
SITE ID;
OTHERWISE
MUST BE OFF
5800RP_dip-00-002-V0
Figure 3 5800RP DIP Switch
LED FUNCTIONS
LED
Activates Upon
Green
Normally on (lighted) when power (AC or battery) is
present. Flickering indicates RF is being processed.
Yellow
Normally off. Blinks to indicate that an RF
message is being sent by the 5800RP.
Red
Normally off. Turns on (lighted) when setting Site
ID. See the Setting the Site ID section for details.
Red
RF Interference
Lights when RF activity is present.
PROGRAMMING AND OPERATIONAL NOTES
Non-UL Installations
(DIP switch 2 must be OFF during normal operation)
1. Set DIP switch 2 to OFF.
2. If module supervision is desired, assign the 5800RP to a zone for
sending check-in, low battery
†
, AC loss, and RF jam messages,
and enroll its serial number. When prompted, toggle the tamper
switch to enroll the serial number. The yellow LED should blink
on when messages are sent.
Program the zone as follows:
Zone Type
Input Type
Loop
8
(24-hour aux)
3
(supervised RF)
1
•
The 5800RP reports AC loss and RF jam conditions as “low
battery” status, which is also displayed on the control’s keypads.
This prevents either condition from causing an alarm when the
control is armed.
•
The 5800RP will not repeat a message that has already been
repeated.
UL Installations
(DIP switch 2 must be ON during normal operation)
1. Supervision: Module supervision is required using the module’s
built-in serial numbers, which are enrolled in 4 zones as follows:
– Assign the first serial number to a zone for sending low
battery
†
and supervision check-in messages.
– Assign the second serial number to 3 zones for sending
tamper, AC loss, and RF jam messages.
When prompted, toggle the tamper switch to enroll the serial
numbers.
Program the zones as follows:
First Serial Number
Set DIP switch 2 to OFF, then enroll as follows:
Zone
Zone Type
Input Type
Loop
Low Battery/
Check-in Zone
8
(24-hour aux)
3 - RF
(supervised RF)
1
Second Serial Number
Set DIP switch 2 to ON, then enroll as follows:
(keep switch 2 in the ON position when enrolling is complete)
Zone
Zone Type
Input Type
Loop
Tamper Zone
5
(trouble by day /
alarm by night)
4 - UR
(unsupervised RF)
1
AC Loss Zone
8
(24-hour aux)
4
- UR
2
RF Jam Zone
8
(24-hour aux)
4 - UR
3
For easy identification of these messages, program alpha
descriptors at the control for each zone, using words such as
“REPEATER LOW BATTERY, REPEATER AC LOSS, etc.
† If an actual low battery condition is reported, it takes up to 12
hours after AC power is restored for the low battery restore
message to be sent (requires 12 hours for fully recharged battery).
2. Power Supply: Use a class 2 Listed Burglar Alarm power
supply for UL installations.
3. Control Panel’s Current Drain Calculation: In order to
properly choose the correct backup battery capacity for systems
using a 5800RP in UL installations, use the connected keypad’s
maximum alarm (sounder on) current rating, not the keypad’s
standby current rating, when calculating the control panel’s
total current drain. This is necessary because AC loss at the
5800RP causes the keypad to beep.
SPECIFICATIONS
Dimensions:
7-3/8" W x 4-3/8"
(10-7/8” w/antennas)
H x 1-7/16" D.
188mm W x 112mm H
(277mm w/antennas)
x 37mm D.
Input Voltage: 12VDC or 9VAC, 15VA (from separate power
supply such as ADEMCO 1332).
Current:
80mA
Battery Pack: rechargeable, part number K0257
Range:
200ft (60m) nominal indoors from wireless devices
(the actual range to be determined with the
security system in the TEST mode).
www.PDF-Zoo.com