background image

&=

6HYHQ=RQH&HOOXODU

&RQWURO&KDQQHO7UDQVFHLYHU

,QVWDOODWLRQDQG6HWXS*XLGH

12:

352

(1$%/('

3

52*5$00(5/(66

5

(*,675$7,21

2

37,21

 

 

 
 

 

K4426CZ 9/01 

 

Summary of Contents for 7845CZ

Page 1: ...6HYHQ RQH HOOXODU RQWURO KDQQHO 7UDQVFHLYHU QVWDOODWLRQ DQG 6HWXS XLGH 12 352 1 352 5 00 5 66 5 675 7 21 237 21 K4426CZ 9 01...

Page 2: ...7845CZZ Installation and Setup Guide ii...

Page 3: ...ng 5 1 Introduction 5 1 Programming 5 1 Using the Programmerless Registration Option 5 1 Using a 7720P Programming Tool 5 2 Password Protection 5 3 Primary Account Information Questions 1 3 5 4 System...

Page 4: ...Radio Supervision 7 4 SECTION 8 8 1 Programmer Keyboard Commands 8 1 SECTION 9 9 1 Troubleshooting 9 1 SECTION 10 10 1 Specifications 10 1 SECTION 11 11 1 UL Requirements 11 1 Power Considerations fo...

Page 5: ...ell Output 4 8 Figure 7 Wiring the 7845CZ Zones 3 through 7 4 9 Figure 8 Wiring the 7845CZ to Trip a Control Panel Zone for Normally Closed Fault Required for UL Installations 4 10 Figure 9 Powering t...

Page 6: ...ment 4 2 Table 3 Initial Power Up Bar Graph and Radio Status LED Sequence 4 4 Table 4 Maximum Wire Run Length 4 7 Table 5 7845CZ Programming Defaults Summary for Zone Mode 5 2 Table 6 7720P Normal and...

Page 7: ...ts intended end point Control Channel Any one of several dedicated RF channels that are used by a cellular radio to register its MIN with a local cell and to periodically check in with that cell The c...

Page 8: ...viii...

Page 9: ...the control channel a true phone call is never placed This eliminates delays due to busy or saturated cells where no voice channels are available The 7845CZ is compliant with the MicroBurst standard f...

Page 10: ...ort transmissions and will draw up to 400mA from the DC source for up to 3 seconds at a time A programmable feature allows the installer to limit input current to 100mA when the unit is powered from a...

Page 11: ...oduct you must carefully observe service availability signal strength and transmission ability Verify MicroBurst coverage using the radio status LEDs as shown at right or use the B command on the 7720...

Page 12: ...ming Tool reset the radio by cycling the power off then on press Enter during the initial power up sequence to enter Programming mode Program the 7845CZ as described in the Programming section 5 Regis...

Page 13: ...paragraph in Section 4 This can take several minutes 2 Find Coverage and Select a Site IT S ALL ABOUT COVERAGE To be successful using this product you must carefully observe service availability signa...

Page 14: ...N CITY CODE CS ID SUBSCRIBER ID TIME ZONE The AlarmNet personnel will first determine if the subscriber number provided is valid If the number is not valid the central station must provide a new numbe...

Page 15: ...registered and tamper reporting has been enabled The RSSI bar graph which is intended to be used as an installation tool and troubleshooting aid becomes active LOCKING TAB LOCKING TAB See Figure 1 to...

Page 16: ...nal level is consistently better than 3 bars or 94dBm as measured with the 7720P The 7845CZ can function properly with the signal strength level as low as one half bar yellow blinking but this is an i...

Page 17: ...king and red lit This indicates the 7845CZ is functioning but not yet initialized The 7845CZ then begins its initialization sequence During this process the 7845CZ is verifying its Mobile Identificati...

Page 18: ...Green lit unregistered radio Green blinking service request successful A side Green not lit previously registered radio Yellow lit request for service pending A side Yellow blinking A side twice per s...

Page 19: ...idation is a low priority receipt from AlarmNet to the 7845CZ and may take several minutes to receive If AlarmNet does not validate a message within 90 seconds the 7845CZ retransmits the test message...

Page 20: ...inimum signal strength level is observed there is access to the 7720P programming port and tamper switch all LED displays can be observed antenna is free from any interference Once the 7845CZ has been...

Page 21: ...in V trigger mode the positive triggering voltage from the control panel must be within 4 5V 14 2V Trigger levels above this range may cause permanent damage to the unit Trigger levels below this ran...

Page 22: ...GND BELL GND Z1 CONTROL PANEL 7845CZ LJXUH LULQJ WKH RQH DQG QSXW IRU D URXQG 7ULJJHUHG HOO 2XWSXW GND must be connected to the control panel s electrical ground as shown in Figures 5 through 9 and no...

Page 23: ...IN RADIO FAULT OUT ADEMCO CONTROL WITH VOLTAGE TRIGGER OUTPUTS J7 1 OUT 1 OUT 2 OUT 4 OUT 3 30 25 20 15 10 5 1 1 7845CZ Z3 Z7 ARE VOLTAGE TRIGGER 4 5 14 2V OR GROUND INPUTS 2 Z1 Z2 Z3 ARE PULSED INPU...

Page 24: ...nt Fail safe mode increases the standby current by about 10mA which results in lower battery backup time about 15 in the event of power loss NOT approved for UL installations Run two wires from the 78...

Page 25: ...om the control panel for 3 seconds presents a problem then the response to the current limit question should be YES when the unit is programmed The disadvantage to this selection is that the radio wil...

Page 26: ...sage is transmitted which alerts the central station that this may be the radio s last message When the battery reaches 5 0V radio transmissions are no longer possible and the system shuts down If sys...

Page 27: ...is 5 seconds Additionally the 7845CZ can be programmed to detect a single pulse on the input characteristic of a Panic indication on the Lynx Control Panel If the programming option Lynx Panic is enab...

Page 28: ...cs 00 25 Delay Zn7 secs 00 26 Restore Zn1 Y N Y 27 Restore Zn2 Y N Y 28 Restore Zn3 Y N Y 29 Restore Zn4 Y N Y 30 Restore Zn5 Y N Y 31 Restore Zn6 Y N Y 32 Restore Zn7 Y N Y 33 Telco Chan 00 34 Open C...

Page 29: ...level At this prompt during initial power up you may proceed with programming the 7845CZ Programming is accomplished by answering displayed questions Most questions require only a Y es or N o respons...

Page 30: ...uestion 6 Carrier Select Auto Use the space key to choose the method by which the 7845CZ will select its cellular carrier A side or B side The radio tests for up to three carriers on a given side and...

Page 31: ...ed If it is registered it goes back to the top of the list and tries again Question 7 Flt Time min Enter in minutes 1 99 the time delay before the 7845CZ notifies the control panel that there is loss...

Page 32: ...e input is supervised by a 2K EOL resistor In this configuration the zone can be triggered by NO NC contacts or Open collector ground or voltage trigger outputs V For installations where the alarm con...

Page 33: ...e transmitted See Questions 20 through 26 to choose reporting zones The chosen zones are reported ONLY when the system is armed The system is considered armed when the voltage is applied to the arm di...

Page 34: ...an 15 is automatically changed to 15 Enter 0 for no delay Question 30 Delay Zn6 secs Enter reporting delay from 1 to 15 seconds for zone 6 An entry greater than 15 is automatically changed to 15 Enter...

Page 35: ...Question 40 Open Close Zone 00 Enter the open close reporting zone number Zones 1 and 2 CANNOT be used If the Lynx Panic feature is enabled Zone 3 cannot be used If the Arm Disarm feature is enabled Z...

Page 36: ...e ones programmed in Questions 1 through 3 Primary Account Information Question 53 2nd Sub ID Enter the4 digit customer account number for the second central station 0001 9999 This ID number combined...

Page 37: ...u want to change the password for the current programming menu If Y es is pressed you are prompted to enter the new password twice as confirmation To clear an existing password answer Y to the CHG PAS...

Page 38: ...7845CZ Installation and Setup Guide 5 12...

Page 39: ...t lit The registration process consists of transmitting three messages in succession and receiving a registration validation from AlarmNet Control It can take several minutes to complete Initiate the...

Page 40: ...is displayed At this point the 7845CZ is in full service and available for alarm reporting to the central station 3RVVLEOH UURUV MIN Exists This prompt appears only if this is a test registration and...

Page 41: ...ration at this point whether successful or unsuccessful results in a radio substitution alarm transmission to the central station Pressing Y allows you to continue registration Pressing N aborts the r...

Page 42: ...7845CZ Installation and Setup Guide 6 4...

Page 43: ...nking Successful message transmission Green Lit with Yellow blinking Network contact but radio is unregistered Blinking On or Off Randomly Transmitter is on the air when an unregistered 7845CZ blinks...

Page 44: ...sec Program mode accessible radio previously unprogrammed Bar Graph Indications Signal Strength Viewed with the cover removed refer to the Removing the Cover paragraph in Section 3 this display consi...

Page 45: ...cessful Normal Operation With the 7845CZ installed programmed and registered and after a successful transmission of the Power on Reset message the 7845CZ enters normal operation Normally with good cel...

Page 46: ...or LED patterns If an alarm is not successfully transmitted before the old alarm time expires the radio fault goes to its programmed fault state and the red LED lights Any time a transmission is unsuc...

Page 47: ...s in contact with a local cell but has no AlarmNet service Z A or B carrier NO CONTACT MIN xxx xxx xxxx NO CONTACT indicates that the 7845CZ has lost contact with the local cell and AlarmNet C NET TIM...

Page 48: ...Restore 6 Previously Reported Event Will probably not be displayed due to speed of radio System Status Display Interpretation for S Command Tm Tamper status follows high speed format codes above Dc R...

Page 49: ...ion reporting as 5555 5555 9 Functional for unregistered 7845CZs only Refer to Section 6 Registration T Test Alarm Sent Test Alarm Sends a Test alarm to AlarmNet Functional for registered 7845CZs only...

Page 50: ...7845CZ Installation and Setup Guide 8 4...

Page 51: ...ellular coverage Run 7845CZ with a charged battery outside of the building Poor location for radio Run 7845CZ with a charged battery outside of the building Incorrect Carrier Select Option If A only o...

Page 52: ...tage and make sure if a 7720V2TR is used that it is not on a switched outlet Environment is too hot or too cold If temperature exceeds 30 C to 60 C battery capacity and or life is diminished Replace b...

Page 53: ...tallation Site paragraph in Section 4 Move the 7845CZ until RSSI level and transmission success rates are acceptable Check antenna and power connections Installation site has obstructions that come an...

Page 54: ...he radio is connected the control panel s signal ground not earth ground Zone setting does not match its physical connection configuration Make sure that the program med setting EOLR V or V matches th...

Page 55: ...n from the power supply Radio fault output Open collector Input triggering levels Voltage ground or contacts can trigger 2K EOL supervised Zones 3 7 Zones 1 and 2 pulsed RF power output 600mW Frequenc...

Page 56: ...7845CZ Installation and Setup Guide 10 2...

Page 57: ...lations must be in accordance with the National Electrical Code and UL1641 Installation and Classification of Residential Burglar Alarm Systems The antenna cable between the 7845CZ unit and the remote...

Page 58: ...arm Systems the 7845CZ must be powered either from a UL Listed Burglar Alarm Control unit or a Listed burglar alarm power supply provided with battery backup power UL 603 See Figure 11 Figure 12 for C...

Page 59: ...ANTENNA 7825 OC UL LISTED CABINET GND ZONE V GND BATT RADIO FAULT TB1 12V GND BATTERY ADEMCO K4362 LISTED PULL BOX WITH COVER LISTED TRANSFORMER NOTE INSTALLING THE TRANSFORMER IN A PULL BOX IS A ULC...

Page 60: ...the Canadian Electrical Code Part I and the Canadian Standard CAN ULC S302 M91 the Standard for the Installation and Classification of Burglar Alarm Systems For Financial and Commercial Premises Safes...

Page 61: ...lity outdoor antenna installed Reorient the receiving antenna until interference is reduced or eliminated Move the radio or television receiver away from the receiver control Move the antenna leads aw...

Page 62: ...FACE HEREOF IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED OR UPON ANY OTHER BASIS OF LIABILITY WH...

Page 63: ...IF CURRENT LIMIT USED GND PULSED ZONE INPUTS ZONE1 ZONE 2 ZONE 3 IN TAMPER TEST SWITCH ANTENNA USE K4139 PROVIDED OR K3209 RUBBER DUCK OR 7805OC VOLTAGE TRIGGER INPUTS 4 5 14 2V OR GROUND J2 PROGRAMMI...

Page 64: ...l K4426CZ 9 01 165 Eileen Way Syosset NY 11791 Copyright 2001 PITTWAY CORPORATION...

Reviews: