15
–
AUX. POWER
OUTPUT
10.5-13.8VDC
600mA MAX.
(500mA MAX.
FOR UL
INSTALLATIONS)
INTERRUPTS
FOR 4-WIRE
FIRE ALARM
RESET. ALL
CIRCUITS ARE
POWER
LIMITED.
NOTE:
KEYPAD(S)
CURRENT
AND ALL OTHER
DEVICES
DRAWING
POWER FROM
TERMS 4 & 5
MUST BE
INCLUDED IN
AUX CURRENT
DRAIN
CALCULATIONS.
OPTIONAL
FOR UP TO 30 ADDITIONAL ZONES
(ONE FROM EITHER OR BOTH GROUPS)
ADEMCO 5881* Type
RF RECEIVER
WIRELESS ZONES
5881L: UP
TO
8
5881M: UP
TO
16
5881H:
UP TO 30
* 5882 IN CANADA
ADEMCO 4219
WIRED EXPANSION MODULE
(8 ADD'L EOLR WIRED ZONES)
-OR-
ADEMCO 4229
WIRED EXPANSION/RELAY MODULE
(8 ADD'L EOLR WIRED ZONES PLUS 2
OUTPUT RELAYS)
-OR-
ADEMCO 4204 RELAY MODULE
(4 OUTPUT RELAYS)
BLK
RED
GRN
YEL
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
EARTH
GROUND
SEE
INSTRUCTIONS
FOR PROPER
GROUNDING
TELEPHONE WIRING
(VIA RJ31X* JACK AND DIRECT
CONNECT CORD)
*CA38A IN CANADA
DOC LOAD NO.: 3
REMOTE KEYPADS
USE 6148 OR 6160
KEYPADS. LOCAL
PROGRAMMING MUST
BE DONE WITH A 6160
CONNECTED TO KEYPAD
TERMINALS, BUT NEED
NOT REMAIN IN THE
SYSTEM.
BLACK: KEYPAD GROUND (–) RETURN
RED: KEYPAD PWR (+)
GREEN: DATA IN FROM KEYPAD
YELLOW: KEYPAD DATA OUT
REMOTE
KEYPAD
}
WARNING:
TO PREVENT RISK OF
SHOCK, DISCONNECT TELEPHONE LINE
AT TELCO JACK BEFORE SERVICING
THIS UNIT.
BATTERY
12V, 4AH
–
+
–
+
CONNECTOR
TABS
PLUG-IN TRANSFORMER
16.5VAC, 25VA (e.g. ADEMCO
No. 1321, USE No. 1321CN IN
CANADA)
TO 110VAC
UNSWITCHED
OUTLET (24HR)
–
+
BLK
RED
GRN
YEL
TO TERM 4
TO TERM 5
TO TERM 6
TO TERM 7
BLK
RED
GRN
YEL
AND/OR
SET RECEIVER’S
DIP SWITCH FOR
DEVICE ADDRESS
OF “0”.
SEE
INSTRUCTIONS.
THIS EQUIPMENT SHOULD BE INSTALLED IN
ACCORDANCE WITH THE NATIONAL FIRE PRO-
TECTION ASSOCIATION’S STANDARD 72, CHAP-
TER 2 (NATIONAL FIRE PROTECTION ASSOC.,
BATTERYMARCH PARK, QUINCY, MA 02269).
PRINTED INFORMATION DESCRIBING PROPER
INSTALLATION, OPERATION, TESTING, MAINTE-
NANCE, EVACUATION PLANNING AND REPAIR
SERVICE IS TO BE PROVIDED WITH THIS
EQUIPMENT.
RING
(GRAY)
TIP
(GREEN)
RING
(RED)
INCOMING
PHONE LINE
HANDSET
BLACK
RED
–
+
2000
OHMS
EOLR
2000
OHMS
EOLR
ZONE 1
ZONE 2
HI
LO
HI
LO
2000
OHMS
EOLR
2000
OHMS
EOLR
ZONE 3
ZONE 4
HI
LO
HI
LO
2000
OHMS
EOLR
2000
OHMS
EOLR
ZONE 5
ZONE 6
HI
LO
HI
LO
• MAXIMUM LOOP RESISTANCE: (EACH ZONE) 300 OHMS
(PLUS EOLR)
• RESPONSE, ZONES 1-6: 10, 350, OR 700 MSEC
(PROGRAMMABLE)
VISTA-15/VISTA-15CN SUMMARY OF CONNECTIONS
USE UL LISTED
LIMITED ENERGY
CABLE FOR ALL
CONNECTIONS
BATTERY FUSE
FOR REPLACEMENT,
USE SAME VALUE
(e.g. ADEMCO No. 90-12)
9-PIN CONNECTOR
USED FOR 4300
TRANSFORMER
CONNECTIONS (FOR
OPTIONAL POWER LINE
CARRIER DEVICES)
SEE INSTRUCTIONS.
1 2 3 4 5 6 7 8 9
USE 4142TR CABLE
USE 4300 TRANSFORMER INTERFACE
IN PLACE OF 1321 WHEN POWER LINE
CARRIER DEVICES ARE BEING USED
(SEE INSTRUCTIONS FOR
CONNECTIONS)
TIP
(BROWN)
}
}
OPTIONAL:
5800TM
TRANSMITTER MODULE (20mA)
(for 5827BD
Wireless Bidirectional Console)
AND/OR
4285/4286 VOICE MODULE (160mA)
AND/OR
LONG RANGE RADIO
MAY ALSO BE CONNECTED. SEE
INSTRUCTIONS ACCOMPANYING
THOSE DEVICES.
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
OPERATION IS SUBJECT TO THE FOLLOWING TWO
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL
INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT
ANY
INTERFERENCE RECEIVED, INCLUDING INTERFERENCE
THAT MAY CAUSE UNDESIRED OPERATION.
COMPLIES WITH FCC RULES, PART 68.
FCC REGISTRATION NO. AC398U-68192-AL-E
RINGER EQUIVALENCE: 0.7B.
WEEKLY TESTING IS REQUIRED TO ENSURE
PROPER OPERATION OF THIS SYSTEM.
3A
ALARM OUTPUT
10.5-13.8VDC, 2A MAX. (600mA MAX. FOR UL
USAGE, INCLUDING AUX POWER)
STEADY FOR BURGLARY/PANIC, TEMPORAL PULSE
SOUNDING FOR FIRE (e.g. USE ADEMCO No. 702
SIREN, OR 12V BELL). SEE INSTRUCTIONS.
CONNECT 2k RESISTOR ACROSS LAST
SOUNDING DEVICE FOR BELL SUPERVISION
CAN BE USED FOR 2-WIRE SMOKE DETECTORS
SET UNIT’S
DIP SWITCH
FOR DEVICE
ADDRESS
OF “1”.
SEE
INSTRUCTIONS.
FOR COMPLETE INFORMATION
SEE INSTRUCTIONS ACCOMPANYING
VISTA-15 CONTROL (K3892)
SMOKE
ZONES 2–7
*
CHARGING
VOLTAGE
13.8VDC MAX.
CHARGING
CURRENT
600mA MAX.
24 HR BATTERY STANDBY REQUIRED FOR FIRE
INSTALLATIONS. USE 12V, 17.2AH BATTERY
FOR 500mA AUX POWER. SEE INSTRUCTIONS.
NORMALLY
NEED NOT BE
REPLACED FOR AT
LEAST 3 YRS.
TO DETERMINE TOTAL
STANDBY LOAD ON
BATTERY, ADD 100mA TO
TOTAL OF AUX. POWER
CUT RED JUMPER
FOR BELL SUPERVISION
FOR CONNECTION OF
OPTIONAL 4285/4286 VOICE MODULE
TO PHONE TERMINALS, SEE
INSTRUCTIONS.
}
NOT USED
BATTERY STANDBY TIME FOR EMERGENCY
BURGLARY MUST BE AT LEAST 4 HOURS.
SEALED LEAD ACID TYPE
BATTERY
AUX PWR
OUTPUT
TERMS
+
-
TO HI SIDE OF SELECTED ZONE
TO LO SIDE OF SELECTED ZONE
+
-
-
+
EOL
POWER
SUPER-
VISION
RELAY
MODULE
A77-716B
5
4
4-WIRE SMOKE
OR COMBUSTION
DETECTOR
2000
OHMS
EOLR
HEAT
DETECTOR
+
RED
BLK
–
*
IF PROGRAMMED FOR FIRE
VIOLET
ECP Compatible
V15_V15CN-SOC-V1