18-1
S E C T I O N 1 8
Final Power-Up Procedure
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
In This Section
♦
General Information
♦
Earth Ground Considerations
♦
Connecting the Transformer
♦
Programming Power and AC Options
♦
Determining the Control Panel Power Supply
Load
♦
Determining the Size of the Standby Battery
♦
Connecting the Battery
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
General Information
•
You can power the control from the supplied 1361 Transformer (1361CN in Canada),
rated 16.5VAC, 40VA, which plugs directly into a 24 hour, 120VAC, 60 Hz outlet.
•
If you are using powerline carrier devices, you must use the 4300 Transformer instead.
UL
Use 1361CN Transformer in Canadian installations.
Power Limiting Outputs
All outputs are power-limited as per UL985/UL1023. The following table shows the
maximum current that may be drawn from each output.
Output
Maximum Current Draw
Auxiliary Power
750mA
Polling Loop
128mA
Alarm Output
1.7A
For Household Fire or Combination Household Fire/Burglary Installation: the total
current drawn from the auxiliary power, the polling loop and the alarm output combined
must not exceed 750mA in order to comply with the battery independence requirements in
UL985.
For Household Burglary Only Installations: the total current drawn from the alarm
output may be up to 1.7A. A battery must be installed to supply combined the auxiliary
power, the polling loop and the alarm output current in excess of 750mA.
Summary of Contents for VISTA-50PEN
Page 2: ...ii...
Page 10: ...VISTA 50PEN Installation and Setup Guide x...
Page 26: ...VISTA 50PEN Installation and Setup Guide 3 4...
Page 42: ...VISTA 50PEN Installation and Setup Guide 6 6...
Page 56: ...VISTA 50PEN Installation and Setup Guide 8 8...
Page 82: ...VISTA 50PEN Installation and Setup Guide 13 4...
Page 110: ...VISTA 50PEN Installation and Setup Guide 18 8...
Page 118: ...VISTA 50PEN Installation and Setup Guide 20 4...
Page 138: ...VISTA 50PEN Installation and Setup Guide 22 18...
Page 166: ...VISTA 50PEN Installation and Setup Guide 25 6...
Page 172: ...VISTA 50PEN Installation and Setup Guide 27 2...
Page 186: ...VISTA 50PEN Installation and Setup Guide 29 8...
Page 192: ...VISTA 50PEN Installation and Setup Guide 30 6...
Page 197: ...B 1 A P P E N D I X B DIP Switch Tables...
Page 200: ...VISTA 50PEN Installation and Setup Guide B 4...
Page 214: ...l K3271 1BX 9 00 165 Eileen Way Syosset NY 11791 Copyright 2000 PITTWAY Corporation...