ZONE 9 RESPONSE TIME
[0]
Enter 1 to set fast response mode (10 msec) for appropriate devices wired to zone 9.
Enter 0 for normal response (350 msec). Must be 0 for UL.
*15
KEYSWITCH ASSIGNMENT
[0]
Enter the partition number 1-8 in which the keyswitch is being used. Otherwise, enter
0.
Requires the use of zone 7 wired loop (zone 7 is no longer available as protection zone
when used for keyswitch operation). If the keyswitch is used, the fire and panic alarm
voltage triggers automatically become ARMING and READY status outputs for support
of the Keyswitch LEDs.
Reports openings/closing by user "0" if reporting is enabled in field *40.
*16
CONFIRMATION OF ARMING DING (part.-specific)
[0]
Enter 1 to enable 1/2 second external alarm sounding ("ding") at the end of exit delay (or
after kissoff from the central station, if sending closing reports). Otherwise enter 0.
Must be 1 for UL commercial burglary installations. Bell test on arming is required in
UL commercial burglary installations.
*17
AC LOSS KEYPAD SOUNDING
[0]
Enter 1 to enable sounding at the keypad (rapid beeping) when AC power is lost
(sounding occurs about 2 minutes after actual AC loss).
Enter 0 if no AC power loss keypad sounding is desired.
*19
RANDOMIZE AC LOSS REPORT
[0]
Selecting this option helps prevent an overload of AC loss messages at the central
station during a community blackout.
Enter 1 to randomize AC loss reporting between 10 and 40 min. after an actual AC loss.
Enter 2 for 6-12 hours after AC loss. Enter 0 for normal AC loss reporting (about 2
minutes after actual AC loss).
*20
VIP MODULE PHONE CODE
[00, 11]
|
|
If a 4285/4286 Voice Module is being used, enter the 2-digit phone code used to access
the system.
Enter 01-09 for first digit, and enter 11 (for
✴
) or 12 (for #) for second digit.
To disable the voice module, enter 00 for the 1st digit and enter 11 for the 2nd digit of
the code (disable code = 00,11). Must be disabled for commercial fire and UL
commercial burglary installations.
*21
PREVENT FIRE TIMEOUT
[0]
Enter 1 to disable (no timeout) the alarm sounder duration for any zone designated as a
fire zone, regardless of partition, so that fire sounding continues until the system is
reset.
Enter 0 if the normal burglary sounder duration (programmed in partition-specific field
*13) should apply to fire alarms.
*22
KEYPAD PANIC ENABLES (partition-specific)
[111]
|
|
95
96
99
Enter 1 to enable the appropriate keypad panics used in this partition.
Otherwise enter 0.
Summary of Contents for VISTA-50PEN
Page 2: ...ii...
Page 10: ...VISTA 50PEN Installation and Setup Guide x...
Page 26: ...VISTA 50PEN Installation and Setup Guide 3 4...
Page 42: ...VISTA 50PEN Installation and Setup Guide 6 6...
Page 56: ...VISTA 50PEN Installation and Setup Guide 8 8...
Page 82: ...VISTA 50PEN Installation and Setup Guide 13 4...
Page 110: ...VISTA 50PEN Installation and Setup Guide 18 8...
Page 118: ...VISTA 50PEN Installation and Setup Guide 20 4...
Page 138: ...VISTA 50PEN Installation and Setup Guide 22 18...
Page 166: ...VISTA 50PEN Installation and Setup Guide 25 6...
Page 172: ...VISTA 50PEN Installation and Setup Guide 27 2...
Page 186: ...VISTA 50PEN Installation and Setup Guide 29 8...
Page 192: ...VISTA 50PEN Installation and Setup Guide 30 6...
Page 197: ...B 1 A P P E N D I X B DIP Switch Tables...
Page 200: ...VISTA 50PEN Installation and Setup Guide B 4...
Page 214: ...l K3271 1BX 9 00 165 Eileen Way Syosset NY 11791 Copyright 2000 PITTWAY Corporation...