VISTA-50PEN Installation and Setup Guide
22-10
*90
SECONDARY SUBSCRIBER ACCT #
|
|
|
|
(partition-specific)
Enter 00-09; B-F (11-15)
[15
15
15
15]
Enter the 3-or 4-digit number (depending on report format) for the secondary subscriber
account: 00-09; B-F (11-15). Each number requires a 2-digit entry to allow entry of
hexadecimal digits (B-F). If a 3-digit number is to be used, enter data only in the first 6
locations, leaving the last two unfilled. Default=15 15 15 15. Erase the field by entering
*90*. NOTE: This field must be programmed if a secondary phone number is used (field
*34). This account number can be the same as the primary account number.
1*07 CHECK OR TRBL DISPLAY
[0]
Enter 1 to display the letters TRBL instead of CHECK when a zone or system trouble
occurs.
Enter 0 to display CHECK.
1*10 FIRE DISPLAY LOCK
[0]
0 = scroll all alarms
1 = lock display of first fire alarm (press * to display other alarms)
1*17 LOBBY PARTITION
[0]
Enter the Common Lobby Partition (1-8).
Enter 0 if none.
1*18 AFFECTS LOBBY (partition-specific)
[0]
Enter 1 if this partition affects the common lobby. Will cause lobby to disarm when this
partition disarms.
Enter 0 if it does not.
1*19 ARMS LOBBY (partition-specific)
[0]
Enter 1 if arming this partition causes the system to attempt to arm the common lobby
partition automatically. Can only arm lobby if all other affecting partitions are armed.
To enable this field, field 1*18 must also be enabled (partition-specific).
Enter 0 if arming this partition will not attempt to arm the common lobby partition.
1*20 EXIT ERROR LOGIC ENABLE
[0]
Enter 1 to enable Exit Error Logic (entry/exit doors and interior zones will be bypassed
if left open).
Enter 0 if Exit Error Logic is not desired. Must be 0 for UL commercial burglary
installations.
1*21 EXIT DELAY RESET
[0]
Enter 1 to reset exit delay to 60 seconds after door is closed.
Enter 0 if exit delay not to be reset. Must be 0 for UL commercial burglary
installations.
1*22 CROSS ZONING PAIR ONE
|
|
Enter the first pair of zones, which must both be faulted within a five-minute period to
cause an alarm.
Enter 00,00 to disable. Must be 00,00 for UL burglary installations.
Summary of Contents for VISTA-50PEN
Page 2: ...ii...
Page 10: ...VISTA 50PEN Installation and Setup Guide x...
Page 26: ...VISTA 50PEN Installation and Setup Guide 3 4...
Page 42: ...VISTA 50PEN Installation and Setup Guide 6 6...
Page 56: ...VISTA 50PEN Installation and Setup Guide 8 8...
Page 82: ...VISTA 50PEN Installation and Setup Guide 13 4...
Page 110: ...VISTA 50PEN Installation and Setup Guide 18 8...
Page 118: ...VISTA 50PEN Installation and Setup Guide 20 4...
Page 138: ...VISTA 50PEN Installation and Setup Guide 22 18...
Page 166: ...VISTA 50PEN Installation and Setup Guide 25 6...
Page 172: ...VISTA 50PEN Installation and Setup Guide 27 2...
Page 186: ...VISTA 50PEN Installation and Setup Guide 29 8...
Page 192: ...VISTA 50PEN Installation and Setup Guide 30 6...
Page 197: ...B 1 A P P E N D I X B DIP Switch Tables...
Page 200: ...VISTA 50PEN Installation and Setup Guide B 4...
Page 214: ...l K3271 1BX 9 00 165 Eileen Way Syosset NY 11791 Copyright 2000 PITTWAY Corporation...