Section 24 – Scheduling Options
24-3
Exception Reports
•
This option allows the reporting of openings and closings to the central station only if the
arming and disarming occurs outside of the predetermined opening and closing time
windows.
•
This option is set in partition-specific field 2*09.
•
The system can be programmed to send No Opening and No Closing reports if the
partition is not armed or disarmed by the end of the corresponding time window.
Time-Driven Events
•
By using the time windows, the system can automatically activate and de-activate relays
at predetermined times to turn lights or other devices on and off.
•
The time-driven events can be activated at different times in relation to the time window:
1.
At the beginning of a time window
2.
At the end of a time window
3.
During a time window active period only (on at beginning of window, off at end)
4.
At both the beginning and end of the time window (e.g., to sound a buzzer at the
beginning and end of a coffee break)
•
The system can perform the same actions on a daily basis, or can be made to perform an
action only once (i.e., turn on the porch light this Wednesday at 8:00 pm).
•
The system also provides up to 20 programmable "timers" available to the end user for
the purpose of activating output devices at preset times and on preset days.
Limitation of Access of Users by Time
•
A user's access can be limited to a certain time period, during which he can perform
system functions. Outside this time, that user's code will be inactive.
•
The system provides up to 8 access schedules, each consisting of two time windows
(typically one for opening, one for closing) for each day of the week and two time windows
for holidays.
•
The access schedules are programmed in the #80 Menu Mode, and enabled for a given
user when that user’s access code is added to the system.
•
If a user tries to operate the system outside of the schedule, the alpha keypad will display
"Access Denied."
Time Window Definitions
General
•
Scheduled events are based on time windows, which are simply periods of time during
which an event may take place.
•
A time window is defined by a “Start” time and a “Stop” time.
•
The system supports up to 20 time windows.
•
The windows are shared by all 8 partitions, and are used when programming the various
schedules (open/close, limitation of access), as well as for time-driven event control.
Summary of Contents for VISTA-50PEN
Page 2: ...ii...
Page 10: ...VISTA 50PEN Installation and Setup Guide x...
Page 26: ...VISTA 50PEN Installation and Setup Guide 3 4...
Page 42: ...VISTA 50PEN Installation and Setup Guide 6 6...
Page 56: ...VISTA 50PEN Installation and Setup Guide 8 8...
Page 82: ...VISTA 50PEN Installation and Setup Guide 13 4...
Page 110: ...VISTA 50PEN Installation and Setup Guide 18 8...
Page 118: ...VISTA 50PEN Installation and Setup Guide 20 4...
Page 138: ...VISTA 50PEN Installation and Setup Guide 22 18...
Page 166: ...VISTA 50PEN Installation and Setup Guide 25 6...
Page 172: ...VISTA 50PEN Installation and Setup Guide 27 2...
Page 186: ...VISTA 50PEN Installation and Setup Guide 29 8...
Page 192: ...VISTA 50PEN Installation and Setup Guide 30 6...
Page 197: ...B 1 A P P E N D I X B DIP Switch Tables...
Page 200: ...VISTA 50PEN Installation and Setup Guide B 4...
Page 214: ...l K3271 1BX 9 00 165 Eileen Way Syosset NY 11791 Copyright 2000 PITTWAY Corporation...