9-1
S E C T I O N 9
Output Devices
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
In This Section
♦
General Information
♦
Installing the 4204 and 4204CF Relay Modules
♦
Installing the FSA Modules
♦
Wiring the 4300 Transformer
♦
Programming Output Devices
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
General Information
The VISTA-50PEN supports up to 96 outputs to activate and de-activate as desired. Each
device must be programmed as to how to act (ACTION), when to activate (START), and when
to deactivate (STOP). Each of these is described later in this section. This is provided by
4204, 4204CF, FSA-8, FSA-24, 4140SN and/or Powerline Carrier devices.
They can be used to:
•
Turn lights on and off
•
Control sounders
•
Control doors
•
Give status indications.
4204/4204CF Relay Modules
Each 4204 module provides 4 relays with Form C (normally open and normally closed)
contacts. Each 4204CF module adds two additional style Y supervised bell outputs to the
system. If 4204CF modules are used exclusively, only relays 1 and 3 on each module can be
programmed. The other 2 relays (relays 2 and 4) on each module are used for supervision
purposes.
FSA Modules
The 8-Zone LED Fire System Annunciator FSA-8 and 24-Zone LED Fire System Annunciator
FSA-24 provide the ability for a fire response unit to identify quickly and easily the
point/zone of a fire. These indicators may be used for other functions as well, such as status
indication. A maximum of 4 FSA modules, in any combination, can be supported. Each FSA
module can support up to 24 LEDs dependent upon model selection.
4101SN Relay Modules
The 4101SN V-Plex Single Output Relay Module is a serial number polling loop output
device. The 4101SN features the following:
•
Form C relay contacts rated at 2A, 28VAC/VDC with contact supervision.
The position of the relay is supervised, but not the actual external contact wiring.
Summary of Contents for VISTA-50PEN
Page 2: ...ii...
Page 10: ...VISTA 50PEN Installation and Setup Guide x...
Page 26: ...VISTA 50PEN Installation and Setup Guide 3 4...
Page 42: ...VISTA 50PEN Installation and Setup Guide 6 6...
Page 56: ...VISTA 50PEN Installation and Setup Guide 8 8...
Page 82: ...VISTA 50PEN Installation and Setup Guide 13 4...
Page 110: ...VISTA 50PEN Installation and Setup Guide 18 8...
Page 118: ...VISTA 50PEN Installation and Setup Guide 20 4...
Page 138: ...VISTA 50PEN Installation and Setup Guide 22 18...
Page 166: ...VISTA 50PEN Installation and Setup Guide 25 6...
Page 172: ...VISTA 50PEN Installation and Setup Guide 27 2...
Page 186: ...VISTA 50PEN Installation and Setup Guide 29 8...
Page 192: ...VISTA 50PEN Installation and Setup Guide 30 6...
Page 197: ...B 1 A P P E N D I X B DIP Switch Tables...
Page 200: ...VISTA 50PEN Installation and Setup Guide B 4...
Page 214: ...l K3271 1BX 9 00 165 Eileen Way Syosset NY 11791 Copyright 2000 PITTWAY Corporation...