VISTA-50PEN Installation and Setup Guide
9-2
•
One class B/style B EOLR-supervised auxiliary input zone.
•
Operating power and communication with control panels via the V-Plex polling loop.
•
Electronics mounted in a small plastic case with tamper-protected cover.
Powerline Carrier Devices
Powerline Carrier devices are controlled by signals sent through the electrical wiring at the
premises via a 4300 transformer. Therefore, if using Powerline Carrier devices, a 4300
transformer must be used in place of the regular system transformer.
This section is used to program relays to activate in response to a programmed condition. The
system can also be programmed to activate relays at specific times by using the
#80 Scheduling
Menu Mode–Time Driven Events
function.
Installing the 4204 and 4204CF Relay Modules
The relay module will not operate until the device address you have set the DIP switches for is
enabled in the control’s
Device Programming
in the
#93 Menu Mode
.
To wire the relay modules, perform the following steps:
Step
Action
1
Set the 4204 or 4204CF’s DIP switches for a device address between 01-15. See
Figures 9-1 and 9-2.
Make sure the address is not being used by another device (keypads, RF
receivers, etc.).
2
Mount the 4204 and 4204CF Modules as per the instructions provided with the
modules.
Connect the module’s wire harness to the keypad terminals (6, 7, 8, and 9). Plug
the connector at the other end of the harness into the module.
If mounted remotely homerun each module to the control. The table
below shows the maximum wire run lengths from the control to each
4204. Refer to the instructions provided with the 4204CF for its
maximum permissible wire lengths.
Wire Gauge
Maximum Length
#22
125 feet
#20
200 feet
#18
300 feet
#16
500 feet
3
Summary of Contents for VISTA-50PEN
Page 2: ...ii...
Page 10: ...VISTA 50PEN Installation and Setup Guide x...
Page 26: ...VISTA 50PEN Installation and Setup Guide 3 4...
Page 42: ...VISTA 50PEN Installation and Setup Guide 6 6...
Page 56: ...VISTA 50PEN Installation and Setup Guide 8 8...
Page 82: ...VISTA 50PEN Installation and Setup Guide 13 4...
Page 110: ...VISTA 50PEN Installation and Setup Guide 18 8...
Page 118: ...VISTA 50PEN Installation and Setup Guide 20 4...
Page 138: ...VISTA 50PEN Installation and Setup Guide 22 18...
Page 166: ...VISTA 50PEN Installation and Setup Guide 25 6...
Page 172: ...VISTA 50PEN Installation and Setup Guide 27 2...
Page 186: ...VISTA 50PEN Installation and Setup Guide 29 8...
Page 192: ...VISTA 50PEN Installation and Setup Guide 30 6...
Page 197: ...B 1 A P P E N D I X B DIP Switch Tables...
Page 200: ...VISTA 50PEN Installation and Setup Guide B 4...
Page 214: ...l K3271 1BX 9 00 165 Eileen Way Syosset NY 11791 Copyright 2000 PITTWAY Corporation...