background image

VISTA-50PEN Installation and Setup Guide

14-2

VistaKey Features

VistaKey features are as follows:

Each VistaKey communicates with the VISTA-50PEN via a special global polling protocol
of the V-Plex polling loop.

In the event local power to the VistaKey is lost, the VistaKey module provides back-up
monitoring of the Access Point door via a built-in V-Plex device that is powered solely
from the polling loop.  It is programmed as a new type of V-Plex device as part of the
control’s V-Plex Device Programming.  A serial number label is affixed to the VistaKey
module for manual entry of its serial number.

 

The VistaKey supports up to 250 cardholders.

 

All configurable options for each VistaKey are accomplished via software, firmware, and
non-volatile memory, eliminating the need for PC board jumpers.

 

Access Point zone numbers (1-15) are assigned via a user-friendly, 16-position rotary
switch.

 

The addition and removal of VistaKey modules from the system is easily accomplished
via the VISTA-50PEN keypad.

 

Each VistaKey provides one open-collector output trigger (sink 12mA @ 12VDC).

Mounting and Wiring the VistaKey

To mount and wire the VistaKey module, perform the following steps:

Step

Action

1

Mount the VistaKey, Door Strike or Mag Lock, and Card Reader.

2

If applicable, mount the Door Status Monitor (DSM) and/or Request to Exit (RTE)
devices.

3

Using Figure 14-1 at the end of this section as a reference, connect the Card
Reader interface cable to TB3, making the +5v or +12v connection last.

4

Connect the leads to TB1 in the following order:

a.

All ground leads to terminals 2, 5 and 9).

b.

The (optional) DSM, RTE, and General Purpose leads to terminals 6, 7, and
8, respectively.

c.

Door Strike (or Mag Lock) lead to terminal 10.

d.

Local +12v or +24v supply lead to terminal 1.

e.

Local +12v or +24v supply lead to the N/C relay terminal 11 (if a Mag Lock is
being used), OR to the N/O relay terminal 10 (if a door strike is being used).

5

Connect the – polling loop and + polling loop leads (from the VISTA-50PEN) to
terminals 4 and 3 respectively.

6

Set the Address Select switch to the desired access door number (1-15).

7

Repeat steps 1 through 6 for each VistaKey being installed.

Summary of Contents for VISTA-50PEN

Page 1: ...DO XUJODU 3DUWLWLRQHG 6HFXULW 6 VWHP ZLWK 6FKHGXOLQJ QVWDOODWLRQ DQG 6HWXS XLGH ARMED READY PANIC OFF AWAY STAY MAX TEST BYPASS INSTANT CODE CHIME READY 1 2 3 6 5 4 8 9 7 0 ALARM CHECK FIRE AWAY STAY...

Page 2: ...ii...

Page 3: ...net Lock 4 1 Grade A Mercantile Premises Listing 4 2 Grade A Mercantile Safe and Vault Listing 4 3 Installing The Control s Circuit Board 4 3 AC Transformer and Battery 4 4 Panel Earth Ground Connecti...

Page 4: ...eneral Information 10 1 Installing the VIP Module 10 2 Installing TeleSmart 10 4 SECTION 11 Audio Alarm Verification AAV Unit 11 1 General Information 11 1 AAV Module Operation 11 1 Audio Alarm Verifi...

Page 5: ...ions 18 2 Connecting the Transformer 18 2 Programming Power and AC Options 18 3 Determining the Control Panel Power Supply Load 18 4 Determining the Size of the Standby Battery 18 6 SECTION 19 The Mec...

Page 6: ...ing a 4100SM Module for Direct Wire Downloading 26 3 SECTION 27 Setting The Real Time Clock 27 1 General Information 27 1 Setting the Time and Date 27 1 SECTION 28 User Access Codes 28 1 General Infor...

Page 7: ...Agency Statements A 1 UL Installation Requirements A 1 UL609 Grade A Local Mercantile Premises Local Mercantile Safe Vault A 1 UL365 Police Station Connected Burglar Alarm A 1 UL611 UL1610 Central St...

Page 8: ...10 5 TeleSmart to Control Connections 10 6 Figure 10 6 TeleSmart RTC and Ground Connections 10 6 Figure 11 1 AAV Connections Using the J7 Trigger 11 2 Figure 11 2 AAV Connections Using a 4204 Relay M...

Page 9: ...onal difficulties This symbol indicates a critical note that could seriously affect the operation of the system or could cause damage to the system Please read each warning carefully This symbol also...

Page 10: ...VISTA 50PEN Installation and Setup Guide x...

Page 11: ...t system via the Vista Gateway Module OR a VistaKey module via the polling loop to provide a fully integrated security and access control system Features Basic Hardwired Zones Provides 9 style B hardw...

Page 12: ...nes 800 831 System Zones 988 999 See the Zone Index Zone Type Defaults section for a full explanation of these zones and specific zone assignments 8 Partitions Provides the ability to control 8 separa...

Page 13: ...der to allow the primary user to program additional user codes into the system at a later time Keypad Panic Keys Accommodates three keypad panic keys 1 A B and 3 C Designated as zones 995 1 996 3 and...

Page 14: ...that activates relays to open access doors e g lobby door Each partition can be assigned to an access control relay By using one Vista Gateway Module VGM the control can be connected to the ADEMCO Pas...

Page 15: ...s Supports the following formats for the primary and secondary central station receivers ADEMCO Low Speed Standard or Expanded Sescoa Radionics ADEMCO Express ADEMCO High Speed ADEMCO Contact ID Long...

Page 16: ...rs can be displayed one at a time by pressing the READY key for 5 seconds This serves as a check for installers to be sure all descriptors are entered properly Improved Downloading Features Uploads an...

Page 17: ...e assigned to one partition it can also be assigned to Partition 9 if Master keypad operation is desired See Master Keypad Setup and Operation later in this section Zones Each zone must be assigned to...

Page 18: ...rea see example that follows explanation This option employs logic for automatic arming and disarming of the common lobby Two programming fields affect the way the common lobby will react relative to...

Page 19: ...Affects Lobby 1 19 Arms Lobby Disarms when partition disarms Attempts to arm when partition arms Can be armed if other partitions disarmed 0 0 NO NO YES 1 0 YES NO NO 1 1 YES YES NO 0 1 ENTRY NOT ALL...

Page 20: ...program a partition to affect and arm the lobby if the users of that partition are expected to be the last to leave the building How User Access Codes Affect the Common Lobby Codes with Global Arming...

Page 21: ...e Programming in the 93 Menu Mode will make that keypad a master keypad A master keypad reflects the status of the entire system Partitions 1 8 on its display at one time This is useful because it eli...

Page 22: ...and or only some partitions are ready The sounder on a master keypad will reflect the sound of the most critical condition on all of the partitions The priority of the sounds is as follows 1 Pulsing f...

Page 23: ...d If this feature is enabled in program field 1 20 the following will occur At the end of the exit delay if a door is left open or an interior zone is faulted the system will start the entry delay per...

Page 24: ...ne protecting the same physical area see warning below Note The four sets of cross zones are programmed in data fields 1 22 1 23 1 24 and 1 25 DO NOT cross zone a fire zone with a burglary zone under...

Page 25: ...ct the premises to verify whether the alarm is valid would hear the phone ringing indefinitely and have to dispatch on the call This option enabled in program field 1 42 attempts to defeat Call Waitin...

Page 26: ...VISTA 50PEN Installation and Setup Guide 3 4...

Page 27: ...pose Before mounting the circuit board remove the metal knockouts for the wiring entry that you will be using DO NOT ATTEMPT TO REMOVE THE KNOCKOUTS AFTER THE CIRCUIT BOARD HAS BEEN INSTALLED Installi...

Page 28: ...between the bell and panel must be run in conduit Remaining wires do not need to be run in conduit 5 All wiring which is not run in conduit must exit from the knockout openings on the bottom or back...

Page 29: ...ip orientation is exactly as shown in figure 4 3 to avoid damage to the clip when mounting screws are tightened This will also avoid problems with insertion and removal of the PC board 2 Insert the to...

Page 30: ...l Power Up Procedure section for battery standby calculations and battery selection table Panel Earth Ground Connections In order for the lightning transient protective devices in this product to be e...

Page 31: ...le is used If more than one keypad is wired to a run then the above maximum lengths must be divided by the number of keypads on the run e g the maximum length is 225 feet if two keypads are wired on a...

Page 32: ...5 2 Make no connection to the keypad blue wire if present 2 Be sure to connect the negative terminal on the power supply unit to terminal 7 AUX on the control SUPPLEMENTARY POWER SUPPLY CONTROL TERMI...

Page 33: ...on the keypad data from the control is not reaching the keypad Please check your wiring Installing Symphony AUI Symphony MUST be connected to a supplementary power supply This is because it requires...

Page 34: ...V0 Figure 5 3 Mounting Symphony Wiring Symphony Connect Symphony in parallel with keypads and other peripheral devices using the ECP bus Symphony is provided with a header connector Wires from the con...

Page 35: ...e terminal of the supplementary power supply to the 12VDC terminal of Symphony red wire 4 Connect the AUX terminal pin 7 to the terminal of the supplementary power supply black wire 5 Connect the term...

Page 36: ...o change that address or to add additional AUIs set the Device Address in the VISTA 50PEN programming for Device Type 01 Alpha Console To program the Symphony in the VISTA 50PEN refer to Device Progra...

Page 37: ...Up to 16 2 wire smoke detectors on zone 1 4 wire smoke or heat detectors on zones 1 8 power to 4 wire smoke detectors must be supervised with an EOL device Up to 50 2 wire latching glassbreak detector...

Page 38: ...zone type 9 the second entry of a User Code OFF sequence at a keypad will interrupt power to these zones to allow detectors to be reset following an alarm Compatible 2 Wire Smoke Detectors You may use...

Page 39: ...es 1 8 can monitor 4 wire smoke detectors N O fire alarm initiating devices or N O sprinkler system supervisory devices You may use as many 4 wire smoke detectors as can be powered from the panel s Au...

Page 40: ...DETECTOR POWER Figure 6 3 4 Wire Smoke Detector Connections Zones 1 8 Installing 2 Wire Latching Glassbreak Detectors to Zone 8 Use zone 8 for connection of compatible 2 wire latching type glassbreak...

Page 41: ...ation Wiring 2 wire Glassbreak Detectors To wire 2 wire glassbreak detectors perform the following steps Step Action 1 Select from the list compatible 2 wire latching glassbreak detectors 2 Connect de...

Page 42: ...VISTA 50PEN Installation and Setup Guide 6 6...

Page 43: ...on the first detector to go into alarm Clearing alarm memory clears the latched LED Polling loop smoke detector LED periodically flashes to indicate communication with the control Installing RPM Devic...

Page 44: ...rors for both wide angle and curtain long range applications Features a nonsupervised auxiliary sensor loop that can accept closed circuit sensors only cannot be used in UL installations 4275 Dual PIR...

Page 45: ...When used in the serial number mode each serial number in the selected group can be assigned to any zone number Loops A B can be programmed for fast 10msec response Can be optionally powered from an...

Page 46: ...20 gauge 950 feet 18 gauge 1500 feet 16 gauge 2400 feet 2 3 Wire each device to the polling loop making sure to use correct polarity when making connections refer to the device s instructions 4 If yo...

Page 47: ...ation information The limits shown below supercede the limits described in the 4297 instructions Do not connect 4297 modules in series RPM Input Polling Loop Extension Polling Loop RPM RPM RPM Extensi...

Page 48: ...each extension loop RPM RPM RPM RPM RPM RPM Extension Loop Limits Each individual loop has the same limits as the input loop Figure 7 3 Polling Loop Connections Using Multiple Extender Modules Note Th...

Page 49: ...es Receivers Recvr Zones 5881L up to 8 5881M up to 16 5881H up to 128 In Canada 5800 systems must use 5882 Series receivers 5882L 5882H Information in this manual relative to the 5881 Receivers applie...

Page 50: ...tion with the receiver a CHECK or TRBL message will appear for the respective receiver supervisory zone 8 2 digit receiver device address for example Device address 05 supervisory zone 805 Supervisory...

Page 51: ...ED DIP SWITCH INSERT IN RIGHT HAND TERMINALS ANTENNAS YELLOW RED BLACK GREEN WIRING OPENING TO CONTROL S REMOTE KEYPAD CONNECTION POINTS EACH RECEIVER MUST BE ON INDIVIDUAL HOME RUN USE MAX OF 220 ft...

Page 52: ...dress Setting 28 cut the white jumper for Address 29 cut both jumpers for Address 30 4 For additional information refer to the 5800TM s instructions The address setting must be enabled in the control...

Page 53: ...ory assigned input loop codes Each of the inputs requires its own programming zone e g a 5804 s four button inputs require four programming zones Transmitters can be programmed as one of the following...

Page 54: ...tire unit must be replaced If using for arming disarming the button must be assigned to a user code when adding a user 5802MN Miniature Personal Emergency Transmitter UR or RF Has single pushbutton Us...

Page 55: ...D Can be used to turn the burglary protection on and off Features the same built in panic functions as wired keypads The keypad is identified as zone 000 on wired keypads when it transmits with a low...

Page 56: ...VISTA 50PEN Installation and Setup Guide 8 8...

Page 57: ...dule adds two additional style Y supervised bell outputs to the system If 4204CF modules are used exclusively only relays 1 and 3 on each module can be programmed The other 2 relays relays 2 and 4 on...

Page 58: ...e 4204 and 4204CF Relay Modules The relay module will not operate until the device address you have set the DIP switches for is enabled in the control s Device Programming in the 93 Menu Mode To wire...

Page 59: ...4 ON ON ON ON ON ON ON ON 5 ON ON ON ON ON ON ON ON ON 1 2 3 4 5 OFF ON 13 14 15 16 NC NC DIP SWITCH FOR SETTING DEVICE ADDRESS AND ENABLING DISABLING TAMPER COVER TAMPER REED SWITCH TB1 TB2 4 PIN CO...

Page 60: ...quad box for FSA 24 3 Connect the module to the control s keypad terminals 6 7 8 and 9 00000 ECP Bus Dip Switch Optional Keyswitch Connection SIDE VIEW All Switches shown in Up position ECP Address 23...

Page 61: ...d STOP event The letter s in parentheses after each function described below such as A after ACTION are those that appear in the various summary displays of programmed data during programming ACTION A...

Page 62: ...ces for ZONE TYPE and SYSTEM OPERATION are listed in Programming Relays later in this section and on the Programming Form 4 PARTITION No P The device s Start ZONE TYPE SYSTEM OPERATION may be limited...

Page 63: ...features Allows the user to receive synthesized voice messages over the phone regarding the status of the security system Allows the user to arm and disarm the security system and perform most other...

Page 64: ...VIP module perform the following steps Step Action 1 If you are mounting the VIP module inside the control cabinet attach it to the cabinet s interior surface with 2 faced adhesive tape You may leave...

Page 65: ...CK TIP RING INCOMING TELCO LINE CALLER ID UNIT IMPORTANT NOTE FOR EXISTING INSTALLATIONS EXISTING WIRES CONNECTED TO THE HANDSET TERMINALS ON CONTROL MUST BE MOVED FROM THERE TO TERMINALS 3 AND 4 ON T...

Page 66: ...x the supplied Summary of Connections label to the module s inside cover or to the inside of the cabinet door Wiring Connections Before making connections power down the control panel To wire the Tele...

Page 67: ...must set TeleSmart keypads to addresses 0 7 only 8 Control Panel Connections see figure 10 5 TeleSmart Plus is powered from the control s 12VDC keypad terminal Connect the control s keypad terminals t...

Page 68: ...OL S KEYPAD TERMINALS Figure 10 5 TeleSmart to Control Connections REAL TIME CLOCK RTC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 EARTH GROUND TYPICAL CONTROL S AC TERMINALS Figure 10 6 TeleSmart RT...

Page 69: ...AAV Module Operation After all messages have been sent during a reporting session to the primary phone number the control will trigger the AAV if at least one of the messages was an Alarm report If C...

Page 70: ...falling edge which is set in DIP switch settings shown 685 Receiver software must be rev 4 6 or higher Earlier versions will not hold the phone line connection Contact ID code for Listen in to Follow...

Page 71: ...16 17 27 26 28 29 30 ZONE 5 J7 DIP Switch 1 2 3 4 5 6 ON CONTROL EARTH GROUND RED R GREEN T RJ31X EDGE TRIGGER YELLOW PIN 3 SYSTEM POWER RED SYSTEM GROUND BROWN BROWN RED TIP RING EAGLE SUPPLIED CABLE...

Page 72: ...d the EOLR must be removed regardless of whether or not EOLRs have been enabled in field 41 Zone 5 is no longer available as a protection zone If using a 4204 relay instead of the J7 trigger program t...

Page 73: ...PC computer used to direct wire download the panel s programming information via the 4100SM Interface Module The trigger output ratings are listed below Note that all outputs are power limited Output...

Page 74: ...J7 connector trigger output 1 to auxiliary power and to the RING side of the telephone line see figure 12 2 2 Determine which side of the telephone line is the RING side by connecting the lead of a DC...

Page 75: ...OR TO OPERATE A KEYSWITCH SEE FIELD 15 BLACK AMSECO PAL 328N PIEZO SOUNDER _ RED TO AUX POWER TERMIANL 6 10mA CURRENT DRAW Figure 12 3 Remote Keypad Sounder Wiring Remote Keyswitch An optional UL Lis...

Page 76: ...rtition The keyswitch LEDs indicate the partition status see table below Faulted zones must either be corrected or bypassed before the system will arm Keyswitch Operation With Alarms Present A momenta...

Page 77: ...ition The fire and burglary audible panic alarm triggers remain HIGH until a User Code OFF is entered in all enabled partition s which display these conditions The silent panic duress trigger works th...

Page 78: ...L Figure 12 6 Connections to 7920SELong Range Radios 7720 ULF RADIO SEE 7720 ULF INSTRUCTIONS FOR MORE DETAILED INSTALLATION INFORMATION FAULT 4142TR CABLE FAULT FAULT ZONE 1 ZONE 2 ZONE 3 GROUND RED...

Page 79: ...57 respectively The Dynamic Signaling feature is designed to reduce the number of redundant reports sent to the Central Station The feature is described as follows Dynamic Signaling Delay Field 56 Sel...

Page 80: ...split reporting is selected for the VISTA 50PEN then the LRR will follow that option The radio will send the appropriate reports to the primary and secondary central stations Supervision The data lin...

Page 81: ...has been detected 7 LRR CRC is bad The radio s EEPROM is corrupt the internal CRC is bad Items 2 and 3 require factory service Items 4 and 5 could be the result of a bad or low battery Item 6 check t...

Page 82: ...VISTA 50PEN Installation and Setup Guide 13 4...

Page 83: ...e The VISTA 50PEN processes fire burglary arm disarm and other information The VistaKey module and PassPoint ACS process card reader information and control the locking and unlocking of doors DO NOT U...

Page 84: ...ed via the VISTA 50PEN keypad Each VistaKey provides one open collector output trigger sink 12mA 12VDC Mounting and Wiring the VistaKey To mount and wire the VistaKey module perform the following step...

Page 85: ...ICE COMPLIES WITH PART 15 CLASS A LIMITS OF FCC RULES OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS 1 IT MAY NOT CAUSE HARMFUL INTERFERENCE 2 IT MUST ACCEPT ANY INTERFERENCE THAT MAY CAUSE UNDE...

Page 86: ...ed on the door where the status of the switch will be different while the door access point is in an open condition 12 VistaKey Request to Exit RTE Use this input type to map an uncommitted RTE zone t...

Page 87: ...able to control the following on the PassPoint ACS Access Points The PassPoint ACS is able to control the following on the VISTA 50PEN Relays Arming disarming schedules Keypad Display See the documen...

Page 88: ...oor Code 73 Code 74 access point These entries allow a user to gain access to an access point Code 75 access point function The selectable functions available are Grant Protect Bypass Selecting Grant...

Page 89: ...procedure An RF transmitter will not provide access or grant if the system is in any test mode Using Wireless Keypads Wireless keypads 5827 5827BD can provide another way of entering or exiting the pr...

Page 90: ...seconds by entering User Code 0 Programming the Control for Stand alone Access Control Step Action 1 Enter Output Programming in the 93 Menu Mode 2 Program the output type as 1 2 or 3 3 For type 1 pro...

Page 91: ...ary power polling loop and alarm output combined must not exceed 750mA For household burglary installations the total current drawn from the alarm output must not exceed 1 7A A battery must be install...

Page 92: ...to the alarm output as shown in Figure 15 1 Wire nonpolarized burglary indicating devices to the alarm output using a polarizing diode two 2A diodes supplied as shown in Figure 15 2 Program Zone 970 w...

Page 93: ...Household Fire Burglary Installations For installations which must provide UL Listed protection the total current drawn from the alarm output auxiliary power output and polling loop combined must not...

Page 94: ...OLARIZED BURGLARY INDICATING DEVICES POLARIZED FIRE INDICATING DEVICE TO OTHER DEVICES POLARIZING DIODES MUST MOUNT AT INDICATING DEVICE Figure 15 2 Wiring Nonpolarized Burglary Indicating Devices Non...

Page 95: ...face Module Event Log Printer Connections The VISTA 50PEN s event log can be printed on a local serial printer Connect a UL EDP Listed serial printer to the J7 connector using an ADEMCO 4100SM Interfa...

Page 96: ...Ground Pin 7 The 4100SM Module sets these pins high If the printer being used will not operate with these pins high then clip the blue CTS white DSR or red CD jumpers on the 4100SM Module to set the...

Page 97: ...AN LOG BY PART 0 NO 1 8 PART The system allows viewing of any partition s event log Enter the partition number for the partition whose events are to be displayed Entering 0 NO will display all events...

Page 98: ...M on January 1 After the last event in the selected category has been displayed using either the 1 or 3 keys the following will appear for a few seconds END OF EVENT LOG TYPE CCC UUU CLEAR EVENT LOG 0...

Page 99: ...00APG cannot make contact with the paging service it will retry up to 10 times If the interface loses contact with the VISTA 50PEN it will send a message to the paging service to notify the user The p...

Page 100: ...f 4100SM DTR 4 Connect TB1 7 of 4100SM to terminal 7 Auxiliary Power of the control 5 Connect TB1 8 of 4100SM to terminal 6 Auxiliary Power of the control Connecting the 4100APG to the 4100SM To conne...

Page 101: ...a Serial Printer 2 Connect a DB 25 to DB 25 cable from the printer to the 4100SM See figure 17 2 3 Configure the printer for 1200 baud rate seven data bits even parity and one stop bit 7 E 1 J8 Brown...

Page 102: ...7 digits may be entered In field 72 enter the Pager ID number of the paging service for Open Close reports This is the PIN number Up to 10 digits may be entered In field 73 enter the phone number of t...

Page 103: ...er in Canadian installations Power Limiting Outputs All outputs are power limited as per UL985 UL1023 The following table shows the maximum current that may be drawn from each output Output Maximum Cu...

Page 104: ...UL Listed Ideal Model 61 035 or equivalent available at most electrical supply stores Connecting the Transformer Failure to observe the polling loop current rating will cause polling loop malfunction...

Page 105: ...rd against blowing the fuse inside the transformer non replaceable Figure 18 1 1321 Transformer and Battery Connections 1 2 3 4 5 6 7 8 9 G R O U N D G R O U N D O U T 6 I N 2 G R O U N D I N 3 G R O...

Page 106: ...nstruction accompanying the device for the current draw Refer to the POLLING LOOP section for device restrictions for fire and burglary usage Polling Loop Current of Units Total Polling Loop Subtotal...

Page 107: ...Device Model Device Current X of Units Standby Alarm Auxiliary Power Subtotal terminals 6 7 750mA max 3 In table 3 enter devices connected to the Alarm Output Calculate alarm currents then add to get...

Page 108: ...d with this panel The total standby current drawn from the auxiliary power and polling loop outputs combined must be limited to 270mA when 14AH batteries are used and 390mA when 17 2AH batteries are u...

Page 109: ...Total Capacity Add standby and alarm capacities Battery Selection Table Use the Battery Selection Table to select the appropriate battery for the installation Capacity Recommended Battery Comment 4AH...

Page 110: ...VISTA 50PEN Installation and Setup Guide 18 8...

Page 111: ...ber you want to program There are several question and answer modes which we call Menu Modes that can be accessed once Data Field Program Mode has been entered These modes prompt the user for informat...

Page 112: ...a data field press plus the 2 digit field address The field s entries will be displayed but no changes can be made Entry Errors If an address is improperly entered the keypad will display FC If a prog...

Page 113: ...eld is less than the maximum permitted for example a phone number the keypad displays the last entry and waits To proceed enter the next data field you wish to program e g press 08 Partition Specific...

Page 114: ...ptors Custom Index Programming VIP Module substitute words Access Point Programming used for VistaKey modules Access Group Programming used for VistaKey modules Event Action Programming used for Vista...

Page 115: ...Devices 995 1 Panic 996 3 Panic 999 Panic Zone Type Definitions Each zone must be assigned a zone type which defines the way in which the system responds to faults in that zone In addition there are t...

Page 116: ...through which one must pass upon entry or exit to and from the keypad Type 05 Trouble by Day Alarm by Night Provides an instant alarm if the zone is faulted and the system is armed in the AWAY STAY I...

Page 117: ...ng an access point entry e g a door The access point entry relay can be assigned to an access control relay controlled by the VISTA 50PEN ECP relay 4204 or to the access control system independent of...

Page 118: ...VISTA 50PEN Installation and Setup Guide 20 4...

Page 119: ...e 603 800 830 ECP Device Supervisory Zones includes keypads wireless receivers VIP Module relay modules etc 8 2 digit Device Address e g Device Address 01 if supervised is zone 801 The 4285 4286 VIP M...

Page 120: ...pe Defaults Following are the zone type defaults for zones on the VISTA 50PEN Zone Zone Type Zone Zone Type 001 09 002 03 003 03 004 03 005 03 006 03 007 03 008 03 009 03 010 128 00 601 632 00 800 830...

Page 121: ...plied by 15 seconds or 00 for no delay up to a maximum delay of 225 seconds entry 15 multiplied by 15 seconds for zones assigned to Zone Type 01 10 EXIT DELAY 1 partition specific 03 Exit delay define...

Page 122: ...ounding occurs about 2 minutes after actual AC loss Enter 0 if no AC power loss keypad sounding is desired 19 RANDOMIZE AC LOSS REPORT 0 Selecting this option helps prevent an overload of AC loss mess...

Page 123: ...ations 27 TEST REPORT INTERVAL 024 Enter the test reporting interval in hours 001 999 Enter 000 if no test reporting is desired If a test report is desired enter a test code in Report Code Programming...

Page 124: ...a 33 PRIMARY PHONE NUMBER This field is used to enter the primary central station phone number up to 17 digits 0 9 enter 11 for 12 for and 13 for a 2 sec pause This is the phone number the control wil...

Page 125: ...TCH 0 Enter 1 to enable Open Close reporting for the keyswitch Enter 0 if reporting is not desired 41 NORMALLY CLOSED OR EOLR ZONES 2 8 0 Enter 0 if end of line resistors are to be used Enter 1 if end...

Page 126: ...ADEMCO Low Speed 1 Sescoa Radionics 47 SECONDARY FORMAT 1 This field selects the reporting format for the secondary telephone number Enter the appropriate number for the secondary format as follows 0...

Page 127: ...0 Select the initial reporting destination for central station messages 0 Primary Dialer 1 Long Range Radio 58 LONG RANGE RADIO CENTRAL STATION 1 CATEGORY ENABLE Alm Trbl Byp Opn ClsSyst Test Enter 1...

Page 128: ...NE NUMBER FOR OPENS CLOSES This field is used to enter the alpha numeric paging service phone number for Open Close reports Enter up to 17 digits 0 9 enter 11 for 12 for and 13 for a 2 sec pause Do no...

Page 129: ...tem Group 1 in the 93 Menu Mode Programming section for assigning the Test Report Code 84 SWINGER SUPPRESSION partition specific 03 This option limits the number of messages alarms or troubles sent fo...

Page 130: ...if none 1 18 AFFECTS LOBBY partition specific 0 Enter 1 if this partition affects the common lobby Will cause lobby to disarm when this partition disarms Enter 0 if it does not 1 19 ARMS LOBBY partiti...

Page 131: ...sed or enter a macro number 01 32 to execute a particular macro with the D key Instead of the 32 macros each key can be programmed for any of 3 other functions Choice 33 fire sounder silence The key w...

Page 132: ...tion is not desired 1 34 COMM SPLIT REPORT SELECTION 0 This field allows certain reports to be directed to either the primary or secondary phone number Enter 0 1 or 2 in accordance with the following...

Page 133: ...liary sounder ex 706 12 This option applies only to the partition enabled in field 15 Enter 3 if AAV module is being used NOTE Only one of the above options may be active within the system 1 47 CHIME...

Page 134: ...f event for which event logging is desired Otherwise enter 0 Note Events will also be logged into the PassPoint system if installed 1 71 12 24 HOUR TIME STAMP FORMAT 0 Select the type of time stamping...

Page 135: ...d weekends for daylight savings time as follows 1 first 2 second 3 third 4 fourth 5 last 6 next to last 7 third from last Standard setting for U S is 1 5 UL Fields 2 05 2 08 must be set to 0 for UL in...

Page 136: ...d outside the programmed disarm opening window if an alarm has occurred Enter 0 to allow disarming only during the disarm window regardless of system status If field 2 10 is set to 0 for a partition t...

Page 137: ...er 1 to allow burglary and panic alarms that occur on other partitions to be displayed at this partition s keypad s Otherwise enter 0 2 24 DISPLAY TROUBLES OF OTHER PARTITIONS 0 Enter 1 to allow troub...

Page 138: ...VISTA 50PEN Installation and Setup Guide 22 18...

Page 139: ...ogramming Below is a list of the main menu selections For the detailed selections refer to the VISTA 50PEN Programming Guide Menu selections are as follows ZONE PROG 1 YES 0 NO For programming the fol...

Page 140: ...used with the 4285 4286 VIP Module CUSTOM INDEX 1 YES 0 NO For creating custom word substitutes for VIP Module annunciation ACCESS POINT PGM 1 YES 0 NO For defining the parameters for each of the Vist...

Page 141: ...g auto disarming auto bypassing and unbypassing of zones and activating relay outputs using 4204 modules The system uses time windows a programmed period of time with a start and stop time for definin...

Page 142: ...seful if a user must stay on the premises later than usual The auto arm delay and warning periods will begin at the end of the extension Force Arm The force arm option causes the panel to attempt to b...

Page 143: ...tion only once i e turn on the porch light this Wednesday at 8 00 pm The system also provides up to 20 programmable timers available to the end user for the purpose of activating output devices at pre...

Page 144: ...digit entries Mon Tue Wed Thu Fri Sat Sun Hol Op Cl Op Cl Op Cl Op Cl Op Cl Op Cl Op Cl Op Cl 01 04 01 04 01 04 01 04 01 05 02 03 00 00 00 00 Note 00 is entered for those days on which the store is c...

Page 145: ...hin the closing window This option is programmed in partition specific program field 2 09 The following chart gives an example of how the Open Close by Exception reporting works Example of Open Close...

Page 146: ...se Reporting by Exception 2 10 Restrict disarm only during windows Report Code Programming in 93 Menu Mode System Group 3 Scheduling related report codes Event driven relay activation options are prog...

Page 147: ...dules Refer to Open Close Schedules Programming later in this section for detailed procedures Enter 0 to move to the Holidays prompt Holidays 1 Yes 0 No 0 Enter 1 to program holiday schedules Refer to...

Page 148: ...w 01 20 00 Quit 01 Enter the 2 digit time window number 01 20 to be programmed Press to accept the entry Enter 00 at the TIME WINDOW prompt to quit time window programming and display the Quit prompt...

Page 149: ...the time window number 01 20 for the displayed day s opening schedule beginning with Monday Enter 00 if no schedule is desired for a particular day As the number is keyed in the actual time that has b...

Page 150: ...or will be positioned on the tens of months digit Enter the appropriate month then press to proceed to the day field Enter the appropriate day for the holiday Press to accept the entry Part 12345678 H...

Page 151: ...y Close for 2 seconds Relay 04 Relay Close XX minutes set in field 1 74 Relay 05 Relay Close YY seconds set in field 1 75 Relay 06 Relay Group On Relay Group 07 Relay Group Off Relay Group 08 Relay Gr...

Page 152: ...Partition s 42 Enable Access Window for access group Access Group 50 Off Normal Reminder None Starts local keypad beeping if fire off normal condition exists Access Control Commands use only with Vis...

Page 153: ...the relay will pulse for 2 seconds at the beginning of the window signaling the beginning of the coffee break At the end of the window it will pulse again signaling the end of coffee break Automatic...

Page 154: ...e XX minutes 05 Relay Close YY seconds Actions 01 05 If actions 01 05 were selected the prompt at the right will be displayed Enter the relay number Press to accept entry The Time Window prompt appear...

Page 155: ...this timed event is to occur As the number is keyed in the actual time that has been stored for the time window number will be displayed Press to accept entry 01 Active time 0 Enter the activation ti...

Page 156: ...cheduling Menu Mode Installer Code 80 After entering Scheduling Menu Mode press 0 until the Access Sched prompt appears Access Sched 1 Yes 0 No 0 Enter 1 to program access schedules ACCESS SCHED 01 08...

Page 157: ...up to one week Temporary Schedule Worksheet Partition Windows Mon Tue Wed Thu Fri Sat Sun 1 Disarm Window Start Time HH MM Stop Time HH MM Arm Window Start Time HH MM Stop Time HH MM 2 Disarm Window...

Page 158: ...ess to move to the AM PM position Pressing any key in the 0 9 range will toggle the AM PM indication Repeat the procedure for the stop time entry After the windows for that day have been completed the...

Page 159: ...timer number has already been programmed a summary screen will appear In this example 06 Timer 07 00PM Start Time 11 45PM Stop Time PORCH LITE Descriptor for Output Device 4 04 Output Device affected...

Page 160: ...under them As the week progresses the selected days are reset to the inactive state unless the permanent option is selected next screen prompt When completed press to continue 06 Permanent 0 NO 1 YES...

Page 161: ...o not connect to telephone company lines which provide ground start service TERMINALS ON CONTROL EARTH GROUND INCOMING TELCO LINE Handset TIP RING RJ31X JACK PLUG DIRECT CONNECT CORD TIP RING GROUND P...

Page 162: ...tandard report Express 4 2 1400 2300Hz DTMF 10 cps 1400Hz Under 3 secs High Speed 1400 2300Hz DTMF 10 cps 1400Hz Under 5 secs Contact ID 1400 2300Hz DTMF 10 cps 1400Hz Under 3 secs ADVISORY ADEMCO s C...

Page 163: ...LoBat Res SSS S RL SSS S RL SSSS RLLB RLRLRL RL LB Trouble Res SSS S RT SSS S RT SSSS RTt RTRTRT RT t Bypass Res SSS S RB SSS S RB SSSS RBb RBRBRB RB b Where SSS or SSSS Subscriber ID C Close Code 1st...

Page 164: ...W in Channel 3 POWER ON RESET in Channel 4 WALK TEST START END in Channel 8 7 NORMAL ALARM STATUS Channels 1 8 Only 9 TEST REPORT Explanation of Channels 9 15 If there is a 1 in the status channel and...

Page 165: ...AC Loss 343 ACS Module Self Test Fail 354 ACS RS232 Fail 373 Fire Loop Trouble 374 Exit Error by Zone 380 Trouble global 381 Loss of Supervision RF 382 Loss of RPM Supervision 383 RPM Sensor Tamper 38...

Page 166: ...VISTA 50PEN Installation and Setup Guide 25 6...

Page 167: ...le hard disk space and at least 8MB of RAM 12MB is preferred Windows 3 X Windows 95 or Windows NT 2 One of the following modems Hayes Smartmodem 1200 external level 1 2 or higher internal level 1 1 or...

Page 168: ...During the next few seconds the control will process the request making sure certain encrypted information received from the computer matches its own memory e Upon a successful match the control panel...

Page 169: ...panel is accessed successfully a Callback Requested report is sent to the central station if Opening reports are programmed When downloading the keypad displays MODEM COMM After each download or a sa...

Page 170: ...1 2 3 4 5 6 7 8 9 NU J8 CONNECTOR VIOLET GRAY YELLOW RED GREEN BROWN BLUE BLACK I N 2 G R O U N D I N 3 G R O U N D O U T 5 O U T 6 G R O U N D G R O U N D P R I N T E R D T R 4142TR CABLE SUPPLIED WI...

Page 171: ...staller or Master Code 63 Typical display shows TIME DATE THU 12 01 AM 01 01 90 2 The day of the week is automatically calculated based on the date entered Time and date entries are made by simply ent...

Page 172: ...VISTA 50PEN Installation and Setup Guide 27 2...

Page 173: ...hen arming the system The security code must always be entered to disarm the system A user code other than the installer code must be programmed for the Quick Arm feature to function User Codes Levels...

Page 174: ...or 1 May change his own code Can add delete or change Manager or Operator Codes Each user s code can be individually eliminated or changed at any time Open Close reporting of added users are is the sa...

Page 175: ...bove A user may not delete or change the user code of the SAME or HIGHER authority than that which he is assigned A user levels 0 1 2 only may only ADD users to a LOWER authority level A user may assi...

Page 176: ...le User 3 has MASTER authority in Partition 1 and OPERATOR B authority in Partition 2 His user number is the same for both partitions Note that if a user number is already being used in a partition th...

Page 177: ...s user Global Arm 0 NO 1 YES Press 0 NO or 1 YES depending on whether this user will be allowed to arm more than one partition via Global Arm prompts described in the Keypad Functions section The keyp...

Page 178: ...er or Operator Code paragraph Deleting a Master Manager or Operator Code Enter your code 8 User number 002 150 your code again Installer Master or Manager Code but must be code with higher level of au...

Page 179: ...ny zones that were in an alarm condition during the armed period To clear this display simply repeat the disarm sequence The keypads also feature chime annunciation and 3 panic keys for silent audible...

Page 180: ...ure if there are faults in any of the selected partitions the system will enter a Summary Mode in which the faulted zones of all of the selected partitions will be displayed These faults must be corre...

Page 181: ...Guide for a detailed explanation of these functions Delaying Closing Time If open close schedules are used end users can manually delay closing time by extending the closing window by 1 or 2 hours Th...

Page 182: ...escriptors have been displayed Viewing Downloaded Messages Users may occasionally receive a message from their installation company displayed on an alpha keypad When this occurs the keypad will displa...

Page 183: ...y to separate different commands For example you may want to perform the following sequence Desired function Keystrokes GOTO partition 2 Enter 2 Bypass Zones 10 11 Press bypass 6 then the zone numbers...

Page 184: ...allows users to manually activate relays by keypad command using either the keypad or a telephone keypad if VIP Module is used The user will be prompted either by keypad alpha display or telephone voi...

Page 185: ...stant Activation Mode is used to activate outputs bypass zones etc The actions that may be activated by the operator are relay commands arm disarm commands zone bypassing commands and open close acces...

Page 186: ...VISTA 50PEN Installation and Setup Guide 29 8...

Page 187: ...83 Burglary Walk Test Code TEST 5 This test causes the system to sound keypad beeps in response to faults on zones for the purpose of allowing proper zone operation to be checked without triggering al...

Page 188: ...ring the security code and pressing OFF If the system has been programmed for silent panic there will be no audible alarms or displays A report will be sent to the central station however 3 Notify the...

Page 189: ...does not beep reorient or move the transmitter to another location Usually a few inches in either direction is all that is required 3 Mount the transmitter according to the instructions provided with...

Page 190: ...ess zones programmed than the wireless receiver can support If this is not corrected none of the zones in the system will be protected If additional wireless zones are desired use an appropriate recei...

Page 191: ...before you call Technical Support be sure you READ THE INSTRUCTIONS Check all wiring connections Determine that the power supply and or backup battery are supplying proper voltages Verify your program...

Page 192: ...VISTA 50PEN Installation and Setup Guide 30 6...

Page 193: ...et field 24 to 0 to enable tamper detection Attach a door tamper switch supplied to the VISTA 50PEN cabinet backbox For safe and vault installations a shock sensor not supplied must also be attached t...

Page 194: ...0SE in place of the 7720 California State Fire Marshal CSFM and UL Residential Fire Battery Backup Requirements The California State Fire Marshal and UL have regulations which require that all residen...

Page 195: ...for repair If upon disconnection of the Control Panel there is still a problem on the line notify the telephone company that they have a problem and request prompt repair service The user may not unde...

Page 196: ...at riel homologu Cette tiquette certifie que le mat riel est conforme certaines normes de protection d exploitation et de s curit des r seaux de t l communications Le minist re n assure toutefois pas...

Page 197: ...B 1 A P P E N D I X B DIP Switch Tables...

Page 198: ...60 UP UP UP UP 61 UP UP UP UP UP 62 UP UP UP UP UP 63 UP UP UP UP UP UP 64 UP 65 UP UP 66 UP UP 67 UP UP UP 68 UP UP 69 UP UP UP 70 UP UP UP 71 UP UP UP UP 72 UP UP 73 UP UP UP 74 UP UP UP 75 UP UP UP...

Page 199: ...35 UP UP UP 36 UP UP UP UP 37 UP UP UP 38 UP UP UP 39 UP UP 40 UP UP UP UP 41 UP UP UP 42 UP UP UP 43 UP UP 44 UP UP UP 45 UP UP 46 UP UP 47 UP 48 UP UP UP UP 49 UP UP UP 50 UP UP UP 51 UP UP 52 UP U...

Page 200: ...VISTA 50PEN Installation and Setup Guide B 4...

Page 201: ...ming Functions Arming Away Enter Code Away 2 Arming Stay Enter Code Stay 3 Arming Instant Enter Code Instant 7 Arming Maximum Enter Code Maximum 4 Quick Arm Use Key Instead Of User Code Followed by An...

Page 202: ...nly End User Output Device Programming User Code 83 Output Device Control Activate Output Device as Programmed User Code 71 Activate Output Device as Programmed User Code 72 Activate Output Device Man...

Page 203: ...0 mA aux load using 7 AH battery Circuit Protectors PTC circuit breakers are used on battery input to protect against reverse battery connections and on alarm sounder output to protect against wiring...

Page 204: ...LCD off sounder off 150mA Active LCD on sounder off 350mA Alarm LCD off sounder on 200mA Alarm LCD on sounder on 400mA Interface Wiring Red 12VDC input supplementary power supply Blue Not Used Green...

Page 205: ...G 18 3 AC RANDOMIZE 18 3 AC Transformer 4 4 Access Group 28 5 Access Control 1 4 14 1 29 3 C 2 Access Control Commands 24 12 Access Control of an Entry Exit Point 14 6 Access Control of Lighting and A...

Page 206: ...2 Communication Formats 1 5 Compass Downloading Software 26 3 Compatible 2 Wire Smoke Detectors 6 2 Compatible 4 Wire Smoke Detectors 6 3 Compatible 5800 Series Transmitters 8 6 Compatible Alarm Indic...

Page 207: ...TICE A 3 FCC REGISTRATION NO D 1 FEDERAL COMMUNICATIONS COMMISSION FCC STATEMENT A 3 FIRE DISPLAY LOCK 22 10 First Communication 26 2 FIRST TEST REPORT TIME 22 9 Force Arm 24 2 FORCE ARM ENABLE FOR AU...

Page 208: ...t 30 4 On Line Control Functions 26 2 OPEN CLOSE REPORTING FOR KEYSWITCH 22 5 Open Close Reporting 28 3 Open Close Reports by Exception 24 5 OPEN CLOSE REPORTS BY EXCEPTION 22 16 Open Close Schedule 2...

Page 209: ...COUNT 22 6 RINGER EQUIVALENCE D 1 RJ31X jack 10 3 RLY VOICE DESCR 23 2 RTE 14 4 S Scheduling 1 5 24 1 Scheduling Commands C 2 Scheduling Menu Mode 24 6 Scheduling Menu Structure 24 7 SECONDARY FORMAT...

Page 210: ...ne Inputs 14 5 Using the Built in User s Manual 29 4 V View Capabilities 28 1 Viewing Capabilities Of A User 29 4 Viewing Data Fields 19 2 Viewing Downloaded Messages 29 4 Viewing Zone Descriptors 29...

Page 211: ...cannot detect motion or intrusion that takes place behind walls ceilings floors closed doors glass partitions glass doors or windows Mechanical tampering masking painting or spraying of any material...

Page 212: ...E FACE HEREOF IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED OR UPON ANY OTHER BASIS OF LIABILITY W...

Page 213: ...ed type and maximum number of detectors supported 2 3 4 1 2 3 4 5 6 7 8 9 1 Not Used 2 Ground 3 Out 1 Ground Start 4 Ground 5 Out 2 fire 6 Ground 7 Out 3 burg aud panic 8 Ground 9 Out 4 silent panic d...

Page 214: ...l K3271 1BX 9 00 165 Eileen Way Syosset NY 11791 Copyright 2000 PITTWAY Corporation...

Reviews: