Section 14 – Access Control
14-5
VistaKey Dialer Enables
When the VistaKey is installed with an alarm system, the system defaults are set so that the
system does not send reports to the central station. The programming is accomplished in field
1
∗
35 for the following events:
•
ACS Troubles - To enable or disable ACS trouble reporting.
•
ACS Bypasses - To enable or disable ACS bypass reporting.
•
ACS System - To enable or disable ACS system reporting, (i.e., ACS module reset).
•
ACS Alarms - To enable or disable ACS alarm reporting.
•
Dialer (Trace) To enable or disable access grant/denial events sent to the central station.
Access Control Using the PassPoint Access Control System
The VISTA-50PEN interfaces with the PassPoint ACS via the VISTA Gateway Module
(VGM). The VGM is connected between the ECP bus (keypad terminals) of the control and
the network bus of the PassPoint ACS (see Figure 14-2). The control sends the VGM its
status information, event log entries and entry/exit requests, (inputs programmed with
response type Access Point), from keypads, hardwired zones, and RF transmitters. The VGM
then reformats and retransmits this information to the Main Logic Board, (MLB) on the
PassPoint ACS network bus.
The VISTA-50PEN is able to control the following on the PassPoint ACS:
•
Access Points
The PassPoint ACS is able to control the following on the VISTA-50PEN:
•
Relays
•
Arming/disarming schedules
•
Keypad Display
See the documentation that comes with the PassPoint ACS for details.
The PassPoint ACS can dedicate some of its inputs for use as regular VISTA-50PEN
hardwired zones (the zone response type is ACS). The PassPoint ACS can also utilize the
VISTA-50PEN’s dialer for reports to the central station.
Using ACS Zone Inputs
If the PassPoint ACS has uncommitted zones, these may be used by the VISTA-50PEN as
hardwired zones.
Programming the ACS Zone Inputs
Step
Action
1
Enter Zone Programming in the #93 Menu Mode.
2
Program this zone as any other zone. Indicate the input type as ACS (10).
3
Enter the PassPoint ACS’s zone ID (00-31)
See Zone Programming in #93 Menu Mode Programming in the Programming Guide for a
detailed explanation.
PassPoint Dialer Events
All PassPoint ACS events can be sent to the VISTA-50PEN’s dialer via the VGM. These
events will also be logged into the control’s event log. This is enabled in the PassPoint ACS.
See the PassPoint ACS documentation for a detailed explanation.
Wiring the Vista Gateway Module
The Vista Gateway Module is connected between the ECP bus (VISTA-50PEN keypad
terminals) and the network bus of the PassPoint Access Control System. See Figure 14-2 for
the proper wiring connections.
Summary of Contents for VISTA-50PEN
Page 2: ...ii...
Page 10: ...VISTA 50PEN Installation and Setup Guide x...
Page 26: ...VISTA 50PEN Installation and Setup Guide 3 4...
Page 42: ...VISTA 50PEN Installation and Setup Guide 6 6...
Page 56: ...VISTA 50PEN Installation and Setup Guide 8 8...
Page 82: ...VISTA 50PEN Installation and Setup Guide 13 4...
Page 110: ...VISTA 50PEN Installation and Setup Guide 18 8...
Page 118: ...VISTA 50PEN Installation and Setup Guide 20 4...
Page 138: ...VISTA 50PEN Installation and Setup Guide 22 18...
Page 166: ...VISTA 50PEN Installation and Setup Guide 25 6...
Page 172: ...VISTA 50PEN Installation and Setup Guide 27 2...
Page 186: ...VISTA 50PEN Installation and Setup Guide 29 8...
Page 192: ...VISTA 50PEN Installation and Setup Guide 30 6...
Page 197: ...B 1 A P P E N D I X B DIP Switch Tables...
Page 200: ...VISTA 50PEN Installation and Setup Guide B 4...
Page 214: ...l K3271 1BX 9 00 165 Eileen Way Syosset NY 11791 Copyright 2000 PITTWAY Corporation...