58 of 77
FR
3.4. Description of the registers
On switching on the product works according to the last saved configuration (Factory Configuration if it is the first start, or if this configuration
has not been changed). Commands such as Modification TTY<n>=<M> or ATR allow you to change the content of the registers: <n> repre-
senting the number of the register and <m> the value to be assigned. This latter is either a decimal value or a hexadecimal value consistent
with the «encoding» column of the tables below.
Examples:
• ATS300=6 assigns the decimal value 6 in register 300
• ATS320=2 assigns the hexadecimal value 0x02 in register 320
It is imperative to save the parameters with the command AT&W before exiting the Command mode otherwise all changes will be lost.
IMPORTANT: The registers that are not documented (that can appear in the list following the AT/S command) in the paragraphs that follow are
reserved and must not be changed.
3.4.1 Function registers
The list of registers below allows you to change the behaviour of the product application.
Register
Size
(bytes)
Description
Coding
Details
300
1
Transmission period of the Keep Alive
frame
Decimal
Default: 144
Min/max: 1 à 255
Unit:
x 10min if S306=1
x 20s if S306=2
301
1
Transmission period of data sensors
Decimal
Default: 1
Min/max: 0 à 255
Unit:
x 10min if S306=1
x 20s if S306=2
The value 0 means no periodic sending, therefore event
operation
304
2
PIN code
Decimal
Default : 0 (disabled)
Min/max : 0 to 9999
PIN code used with ATPIN command.
Value 0 disables the PIN code.
IMPORTANT: The product does not have a mechanism
to unlock the PIN code if it is activated and the code is
forgotten.
306
1
Global operation
Decimal
Default: 0
Allows the product to be switched into one of the
following modes:
• 0: PARK mode
• 1: Production mode
• 2: TEST mode
• 3: REPLI mode
320
1
Configuration of the internal sensor
Hexadecimal Default: 0x00
Bits 0 to 3: Reserved
Bits 4 to 7: Identifier (free to use)