EN
WMBUS TEMP - Guide utilisateur / User guide version V2.0.0
59 of 77
FR
321
1
Configuring the event behaviour of the
internal sensor
Hexadecimal Default 0x03
Bits 0 to 1: Threshold triggering
• 0 = None
• 1 = Low only
• 2 = High only
• 3 = Low and High
Bits 2 to 7: Reserved
322
1
Configuration of the external sensor
Hexadecimal See details of register 320
323
1
Configuring the event behaviour of the
external sensor
Hexadecimal See details of register 321
324
4
High threshold value of the internal
sensor
Decimal
Default: 300
Min/max: -550 to 1200 (signed value)
Units: tenth of °C
325
1
Value of the high threshold hysteresis
of the internal sensor:
Decimal
Default: 10
Min/max: 0 of 255 (Unsigned value)
Unit: tenth of °C
326
4
Low threshold value of the internal
sensor
Decimal
Défaut: 300
Min/max: -550 à 1200 (Unsigned value)
Unit: tenth of °C
327
1
Value of the low threshold hysteresis of
the internal sensor
Decimal
Default: 10
Min/max: 0 à 255 (Unsigned value)
Unit: tenth of °C
328
4
High threshold value of the external
sensor
Decimal
Dfaut: 300
Min/max: -550 à 1200 (Unsigned value)
Unit: tenth of °C
329
1
Value of the high threshold hysteresis
of the iexternal sensor:
Decimal
Default: 10
Min/max: 0 to 255 (Unsigned value)
Unit: tenth of °C
330
4
Low threshold value of the external
sensor
Decimal
Default: 300
Min/max: -550 à 1200 (Unsigned value)
Unit: tenth of °C
331
1
Value of the low threshold hysteresis of
the exterbal sensor
Decimal
Default: 10
Min/max: 0 à 255 (Unsigned value)
Unit: tenth of °C
332
1
Acquisition period
Decimal
Default: 10
Min/max : 1 à 255
Unité:
x 1minute if S306=1
x 10 secondes if S306=2
333
1
Super-sampling factor
Decimal
Default: 5
Min/max: 1 à 10
Unit: aucune
A consistency check will be performed at the time of the registration of the settings via the AT&W command. If one of the following conditions
is verified, the command will return «W»:
• Period of transmission = 0 (register 301) and no active threshold (registers 321 and 323)
• Two active thresholds (registers 321 and 323), and the value of the high threshold is less than the value of the low threshold.