WMBus Smart Building MOTION - Guide utilisateur / User guide version V1.0.0
65
Page
of 82
FR
3.3.1.04
Registers that configure digital input alarm(s)
Register Size
(bytes)
Description
Encoding
Details
S380
1
Configuration of the
button (Digital Input 1)
Hexadecimal
Default: 0x41
Min/max: <7:4> Debounce time 0: No debounce time
1: 10 ms
2: 20 ms
3: 50 ms
4: 100 ms
5: 200 ms
6: 500 ms
7: 1 s
8: 2 s
9: 5 s
A: 10 s
B: 20 s
C: 40 s
D: 60 s
E: 5 minutes
F: 10 minutes
< 3:0> Type
0 = OFF
1 = Event ON 2 = Event OFF
3 = Event ON/ OFF
S381
2
Button alarm threshold
(Digital Input 1)
Decimal
Default: 1
Min/max: 1 to 65535
The value 1 equals 1 detection
When the Digital Input 1 detection counter becomes greater than this
threshold, an alarm is triggered
S382
1
Configuration of the
terminal block (Digital
Input 2)
Hexadecimal
Default: 0x0
Min/max: <7:4> Debounce time 0: No debounce time
1: 10 ms
2: 20 ms
3: 50 ms
4: 100 ms
5: 200 ms
6: 500 ms
7: 1 s
8: 2 s
9: 5 s
A: 10 s
B: 20 s
C: 40 s
D: 60 s
E: 5 minutes
F: 10 minutes
< 3:0> Type
0 = OFF
1 = Event ON 2 = Event OFF
3 = Event ON/ OFF
S383
2
Terminal alarm thresh-
old (Digital Input 2)
Decimal
Default: 1
Min/max: 1 to 65535
The value 1 equals 1 detection
When the Digital Input 2 detection counter becomes greater than this
threshold, an alarm is triggered