User Guide | COMFORT LwM2M | NB-IoT / LTE-Cat-M1
60
Parameters
Description
Default Configuration
PUSH Mode
If this mode is enabled, the product
controls the data transmissions to
the server
Disabled
PUSH Mode Transmission
Frequency
Frequency of data transmission in
PUSH mode
3600 seconds
Sensor Sampling Frequency
Sampling frequency of
Tempe Humidity values
3600 seconds
High Threshold Detection
Threshold beyond which the
product will trigger a transmission
of the sensor measurement
-
Low Threshold Detection
Threshold below which the product
will trigger a transmission of the
sensor measurement
-
Hysteresis
Hysteresis value for high and low
thresholds
-
Threshold Status
Identifies an error in the
configuration of different
thresholds
-
These parameters can be configured via the NFC IoT Configurator application or the LwM2M server.
Example
The product measures temperature, humidity every 10 minutes.
Alarms are configured for the product to notify the server:
If the temperature exceeds 25°C. This alarm will be disabled if the temperature falls below 24°C.
If the temperature goes below 19°C. This alarm will be disabled if the temperature rises above
20°C.
There are no alarms for humidity.
Configuration of Applicable Parameters to Use
Parameters
Unit
Value
Description
PUSH Mode
-
Enabled
-
PUSH Mode
Transmission Frequency
Seconds
0
No periodic transmission
of T+H
Sensor Sampling
Frequency
Seconds
600
1 measurement every 10
minutes for T+H
Temperature Alarm
Activation
-
Enabled
Temperature alarm
activated
Temperature High
Threshold Detection
°C
25
High threshold to trigger
the alarm is 25°C
The table below lists the parameters to configure for using this transmission mode: