User Guide | COMFORT LwM2M | NB-IoT / LTE-Cat-M1
61
Parameters
Unit
Value
Description
Temperature Low
Threshold Detection
°C
19
Low threshold to trigger
the alarm is 19°C
Hysteresis
°C
1
Hysteresis value is 1°C
Humidity Alarm Activation -
Disabled
Humidity alarm disabled
📱
Configuration via the NFC IoT Configurator App
Go to the "CONFIGURATION" menu of the sensor => Select the "CONNECTIVITY" section
=> Go to the "Protocol" subsection => Configure the "Product-Server Communication"
parameter in "PUSH" mode.
Go to the "APPLICATION" section => Configure the sensor sampling frequency to 600
seconds => Configure the transmission period to 0 seconds.
=> Go to the "TEMPERATURE" section => Enable the high and low threshold alarm mode
=> Configure the high threshold detection to 25°C, the low threshold detection to 19°C, and
the hysteresis to 1°C.
=> Check the threshold status.
=> Apply the new configuration to the product using NFC.
💻
Configuration via a LwM2M Server
URI
Object Name
Resource Name
Access Type
Unit
Description
/34450/0/0
COMFORT
LWM2M mode
R/W
-
1 = Push mode
/34450/0/1
COMFORT
Push period
R/W
seconds
0
/34450/0/2
COMFORT
Sensor sampling
period
R/W
seconds
600
34450/0/19
COMFORT
Temperature:
high threshold
R/W
°C
25
34450/0/20
COMFORT
Temperature:
low threshold
R/W
°C
19
34450/0/21
COMFORT
Temperature:
threshold
hysteresis
R/W
°C
1
34450/0/22
COMFORT
Temperature:
enable alarm
R/W
-
3 = activate both
thresholds