User Guide | COMFORT LwM2M | NB-IoT / LTE-Cat-M1
65
Parameters
Unit
Value
Description
PUSH Mode
-
Enabled
PUSH Mode
Transmission Frequency
Seconds
14400
1 transmission every 4
hours (T+H)
Sensor Sampling
Frequency
Seconds
1800
1 measurement every 30
minutes (T+H)
Temperature Alarm Mode
Activation
-
Enabled
Temperature alarm
activated
Temperature High
Threshold Detection
°C
24
High threshold to trigger
the temperature alarm is
24°C
Hysteresis
°C
2
Hysteresis value is 2°C
Humidity Alarm Mode
Activation
-
Disabled
Humidity alarm disabled
📱
Configuration via the NFC IoT Configurator App
Go to the "CONFIGURATION" menu of the sensor.
=> Select the "CONNECTIVITY" section => Go to the "Protocol" subsection => Configure
the "Product-Server Communication" parameter in "PUSH" mode.
Go to the "APPLICATIVE" section => Configure the sensor sampling frequency to 1800
seconds => Configure the transmission period to 14400 seconds.
=> Go to the "TEMPERATURE" section => Enable the high threshold alarm mode => Set
the high threshold detection to 24°C and the hysteresis to 2°C.
=> Go to the "APPLICATIVE" section => Verify the threshold status.
=> Apply the new configuration to the product via NFC.
💻
Configuration via a LwM2M server
URI
Object Name
Resource Name
Access Type
Unit
Description
/34450/0/0
COMFORT
LWM2M mode
R/W
-
1= Push mode
/34450/0/1
COMFORT
Push period
R/W
secondes
14400
/34450/0/2
COMFORT
Sensor sampling
period
R/W
secondes
1800
34450/0/19
COMFORT
Temperature :
high threshold
R/W
°C
24
34450/0/21
COMFORT
Temperature :
threshold
hystérésis
R/W
°C
2