2.2.2 Periodic transmission with history
The product allows the accumulation of several successive meter values before the periodic transmission of the set of values according to the
following scheme:
Product in standby
Send frame
0x5A and/or 0x5B
Historical
period
reached?
Yes
No
Detected
and validated
pulse?
Counting
of the impulse
Yes
No
No
Number of
recorded values
reached?
Yes
The parameters associated with this mode of operation are:
•
Enabling and Configuring inputs (register 320)
•
Historisation period (register S321)
•
Sending frequency (S301)
•
Anti-bounce timer period (registers S322)
Eg:
Register
Value encoding
Value
Result
S320
Hexadecimal
0x39
Channel A :
• Activated
•
Meter other than gas
•
Tamper input activated
Channel B :
• Activated
•
Gas meter
•
Tamper input disabled
S301
Decimal
4
Sending every 4 historisations (saving)
S321
Decimal
300
Historisation of the data every 10 minutes (300x2 sec-
onds=600 seconds).
S322
Hexadecimal
0x57
Anti-rebound :
•
Channel A = 500ms
•
Channel B = 100ms
Sending according to channel activation:
• 5A frame for channel A
• 5B frame for channel B